2 - INSTALLATION
© Fulton 2018
2-32
VSRT_IOM_2018-1213
MIN 4FT
( 122 CM )
APPROVED EXHAUST
VENT MATERIAL
MIN 4FT / 122 CM
ABOVE AIR
INTAKE PIPING
SCREENED INLET
EXHAUST OUTLET
IF SNOW ACCUMULATION
IS APPLICABLE, OPENING TO BE
1 FT. / 30 CM ( MIN. ) ABOVE
THIS NORMALLY EXPECTED LEVEL.
TYPICAL ROOF PENETRATIONS
( SUGGESTED TERMINATION CONFIGURATIONS )
EXHAUST STACK IS DOWNWIND
OF AIR INTAKE OPENING
VSRT
BOILER
( SIDE VIEW )
NOTE:
AIR INTAKE AND EXHAUST TERMINATION SHOULD BE
SEPARATED AS FAR AS POSSIBLE TO PREVENT FLUE GAS
RECIRCULATION DURING DIFFERENT WIND CONDITIONS.
AIR INLET
NOTE:
1.) When using horizontal runs follow a 1/4" per foot rise to run ratio
2.) Maintain minimum 9" / 22.86 cm air space clearances to combustables,
wires and insulation
3.) Install support straps at 5 FT / 152 CM horizontal intervals and at elbows
Figure 16 - Roof Penetration Details
Содержание VSRT 10
Страница 2: ......
Страница 5: ...1 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 11: ...2 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 44: ...2 INSTALLATION Fulton 2018 2 34 VSRT_IOM_2018 1213...
Страница 45: ...3 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 61: ...4 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 88: ...5 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5 Parts 6...
Страница 89: ...5 WARRANTY Fulton 2018 5 2 VSRT_IOM_2018 1213...