1 - SAFETY & WARNINGS
© Fulton 2018
1-6
VSRT_IOM_2018-1213
Steam Boiler Systems
Warnings and Cautions
The following WARNINGS and CAUTIONS are specific
to Steam Boiler Systems and may also appear in
various chapters of this manual. It is critical that all
personnel read and adhere to all information contained
in WARNINGS and CAUTIONS throughout this manual.
In addition, there are bolded
Notes
throughout the
manual, which are included as additional information
for essential and effective operation and conditions.
!
WARNING
Boiler blowdown water must be cooled to <140
˚
F
(60
˚
C) prior to discharge to a drain, or as required per
local jurisdictional codes. Failure to use an approved
blow off vessel with adequate cooling could cause
personnel/equipment damage.
Improper installation or maintenance of gauge glass
and connections can cause immediate or delayed
breakage resulting in bodily injury and/or property
damage. Only properly trained personnel should
install and maintain gauge glass connections. Wear
safety glasses during installation. Be sure all parts are
free of chips and debris.
!
CAUTION
Where an atmospheric feedwater tank is to be
installed, this should: 1) be vented to a safe location; 2)
have capacity sufficient to satisfy boiler consumption,
as well as maintain proper return tank temperature; 3)
Vent pipe should not be downsized, as it may caused
pressure build up in the tank; 4) Return pipes must
not be insulated as this can cause overheating in the
feedwater tank and potential vapor lock in the pump.
Return pipes should be shielded to prevent burn
hazard.
Gauge glass valves need to be fully open during boiler
operation to prevent boiler damage in case of gauge
glass failure.
After installation is complete and prior to operation,
the pressure vessel should be cleaned or boiled out per
instructions in this manual.
Содержание VSRT 10
Страница 2: ......
Страница 5: ...1 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 11: ...2 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 44: ...2 INSTALLATION Fulton 2018 2 34 VSRT_IOM_2018 1213...
Страница 45: ...3 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 61: ...4 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 88: ...5 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5 Parts 6...
Страница 89: ...5 WARRANTY Fulton 2018 5 2 VSRT_IOM_2018 1213...