INSTALLATION - 2
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
2-33
VSRT_IOM_2018-1213
APPROVED EXHAUST
VENT MATERIAL
WALL
WALL TERMINATION
( WITH SCREEN )
6 IN / 15 CM
MIN
DO NOT PLACE INSULATION IN
REQUIRED AIR SPACE CLEARANCE
BAND SUPPORT
COLLAR
(TYP EACH SIDE)
90° ELBOW
SCREENED AIR INLET
EXHAUST PIPE
WALL PENETRATION
48 IN. / 122 CM.
(MINIMUM)
10 FEET
(MINIMUM)
AIR INTAKE
WALL PENETRATION
WIND DIRECTION
LOCATE INTAKE
UPWIND OF
EXHAUST PIPING
AIR INTAKE & EXHAUST PIPES WALL PENETRATION CLEARANCES
CAUTION:
AIR INTAKE AND EXHAUST TERMINATION SHOULD BE
SEPARATED AS FAR AS POSSIBLE TO PREVENT FLUE GAS
RECIRCULATION DURING DIFFERENT WIND CONDITIONS
NOTE:
MAINTAIN MINIMUM 9"/22.86 CM AIR SPACE
CLEARANCES TO COMBUSTABLES, WIRES AND INSULATION
4 FT / 122 CM ( MINIMUM )
BETWEEN INLET & EXHAUST
OPENING ( SEE BELOW )
AIR INTAKE AND EXHAUST
TERMINATION SHOULD BE
SEPERATED AS FAR AS POSSIBLE
TO PREVENT FLUE GAS
RECIRCULATION DURING
DIFFERENT WIND CONDITIONS.
OPENING 1 FT / 30 CM ( MIN )
ABOVE NORMALLY EXPECTED
SNOW ACCUMULATION LEVEL
RISE TO RUN: 1/4" PER FOOT
Figure 17 - Side Wall Penetration Details
MIN 4FT
( 122 CM )
APPROVED EXHAUST
VENT MATERIAL
MIN 4FT / 122 CM
ABOVE AIR
INTAKE PIPING
SCREENED INLET
EXHAUST OUTLET
IF SNOW ACCUMULATION
IS APPLICABLE, OPENING TO BE
1 FT. / 30 CM ( MIN. ) ABOVE
THIS NORMALLY EXPECTED LEVEL.
TYPICAL ROOF PENETRATIONS
( SUGGESTED TERMINATION CONFIGURATIONS )
EXHAUST STACK IS DOWNWIND
OF AIR INTAKE OPENING
VSRT
BOILER
( SIDE VIEW )
NOTE:
AIR INTAKE AND EXHAUST TERMINATION SHOULD BE
SEPARATED AS FAR AS POSSIBLE TO PREVENT FLUE GAS
RECIRCULATION DURING DIFFERENT WIND CONDITIONS.
AIR INLET
NOTE:
1.) When using horizontal runs follow a 1/4" per foot rise to run ratio
2.) Maintain minimum 9" / 22.86 cm air space clearances to combustables,
wires and insulation
3.) Install support straps at 5 FT / 152 CM horizontal intervals and at elbows
Содержание VSRT 10
Страница 2: ......
Страница 5: ...1 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 11: ...2 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 44: ...2 INSTALLATION Fulton 2018 2 34 VSRT_IOM_2018 1213...
Страница 45: ...3 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 61: ...4 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5...
Страница 88: ...5 1 Section Safety Warnings 1 Installation 2 Operation 3 Maintenance Troubleshooting 4 Warranty 5 Parts 6...
Страница 89: ...5 WARRANTY Fulton 2018 5 2 VSRT_IOM_2018 1213...