Questions? Call (315) 298-5121, or visit us online at www.fulton.com
SECTION 3
RLN-IOM-2012-1205
OPERATION
3-11
§
Central Heat Confi guration (Setpoint)
– (See Figure 20) The highest water
temperature the boiler will try to maintain in relation to the to the Minimum
Outdoor Temperature
§
Time of Day Setpoint –
Forces the Outdoor Reset line to parallel shift down
to a lower setpoint, also known as a night time setback. A contact closure is
required on connector J10 terminals (2&3) to utilize Time of Day setpoint.
Example (See Figure 21): If the outdoor temperature is at 20 degrees Fahrenheit
the boiler temperature will be 172 degrees Fahrenheit. The boiler will modulate
to maintain this temperature and shutdown at 172 plus off Hysteresis, which from
the above Central Heat Confi guration Screen is 10, so the unit would shut down
at 172F +10 (Off Hysteresis) = 182 degrees. The boiler will get a call for heat at
172F+/- 10 (On Hysteresis) = 162.
FIGURE 20 - CENTRAL HEAT CONFIGURATION SETPOINT
FIGURE 21 - EXAMPLE SCREEN
!
WARNING
Non-Fulton product information is for
reference purposes only. No Fulton
document should substitute for full review
of documentation available from the
component manufacturer.
4
CAUTION
Only factory-trained personnel should
attempt to alter password protected Control
preset values.
Содержание Reliance 1000
Страница 2: ......
Страница 4: ...TheFultonCompanies2012 TABLEOFCONTENTS RLN IOM 2012 1205 0 2...
Страница 42: ...TheFultonCompanies2012 OPERATION RLN IOM 2012 1205 SECTION3 3 12...
Страница 50: ...TheFultonCompanies2012 MAINTENANCE RLN IOM 2012 1205 SECTION4 4 8...
Страница 51: ......
Страница 52: ......
Страница 59: ......