J OIL-E-08 2008
Boiler will not
1. Oil tank empty Refill the oil tank. A slight delay in the re-priming
maintain pressure
of the fuel pump may cause the burner
programmer to require resetting before the boiler
operates satisfactorily.
2. Oil Nozzle Check for blocked nozzle. Clean or replace.
3. Oil Valve Check voltage between oil valve leads at
terminal block to be sure oil valve is getting
power.
4. Oil Pump Check for blocked strainer or filter. Remove and
clean. Check for slipping or broken coupling,
tighten or replace. Check for seized pump shaft.
Replace the pump.
5. Dirty Flue Check flue for Carbon build-up or blockage.
Clean flue passages with brush.
6. Pressure Control Disconnect all power to the controller.
Disconnect the wires from the controller.
Place an OHM meter between the switch
terminals. Lower the set point of the controller,
the switch should make. Raise the set point and
recheck, switch should break. If the controller
operates improperly, replace it.
7. Scale buildup in boiler Consult Fulton.
8. Refractory Bricks Check the bricks are not plugged with soot,
cracked or broken into pieces. Clean and
replace as required.
9. Steam Traps Check traps, clean or replace as required.
blowing through
10. Boiler size Boiler may be undersized.
3
3.11 TROUBLESHOOTINg - continued.
Problem Cause Remedy
28
3
3
Содержание 10J
Страница 42: ...J OIL E 08 2008...
Страница 56: ...J OIL E 08 2008 A0 2 1 BOILER OIL 1 2 3 4 5 6 December 12 2004...
Страница 74: ...J OIL E 08 2008 E1 6 1 WATER COLUMN 6 60 December 2004 E1 6 1 12 2004 1 11 6 4 2 9 10 4 6 4 5 3 8 7...
Страница 76: ...J OIL E 08 2008 F1 4 1 WATER LEVEL GAUGE ASSEMBLY 6 60 350mm and 300mm Clifton December 2004...
Страница 84: ...J OIL E 08 2008 H1 1 1 PUMP FEED WATER 1 December 2004...
Страница 86: ......