J OIL-E-08 2008
24
3
3
3.9 DRAININg THE BOILER,
Boilers with manual blowdown valves
CAUTION
Your local regulations could state boiler water above 43
O
C must not be discharged into the drain.
ALWAYS check your local regulations.
1.
Ensure the boiler is cold.
2.
Isolate the boiler electrics at the isolator on the control box door.
3.
Isolate the feed water tank and the feed water pump.
4.
Open the main steam valve and the boiler drain valve.
5.
Open the drain valve on the blowdown vessel.
6.
Open all valves in the drain lines.
Boilers with automatic blowdown systems
1.
The boiler should not be under pressure.
The boiler should be cold.
2.
Close the blowdown isolation valve.
3.
Using a screwdriver located as shown
‘A’
, push up and make a quarter turn,
this will lock the button in position and open the blowdown valve.
4.
Using the blowdown isolation valve to throttle the flow, drain the boiler.
Note:
Skid units and plant rooms have internal drainage systems which require the same procedures.
3.10 LONg TERM SHUT DOWN
To store the boiler in a corrosion-free situation there are three practical solutions:
1.
Fully flood the boiler to exclude as much air as possible.
2.
Drain the boiler completely.
Remove all hand hole and manhole doors.
Open all gas/oil side access doors.
3.
As (2) but also introduce a form of convection heating to the gas/oil and water side.
A very effective solution is to install a string of outdoor type waterproof light bulbs distributed
throughout the boiler.
A
Содержание 10J
Страница 42: ...J OIL E 08 2008...
Страница 56: ...J OIL E 08 2008 A0 2 1 BOILER OIL 1 2 3 4 5 6 December 12 2004...
Страница 74: ...J OIL E 08 2008 E1 6 1 WATER COLUMN 6 60 December 2004 E1 6 1 12 2004 1 11 6 4 2 9 10 4 6 4 5 3 8 7...
Страница 76: ...J OIL E 08 2008 F1 4 1 WATER LEVEL GAUGE ASSEMBLY 6 60 350mm and 300mm Clifton December 2004...
Страница 84: ...J OIL E 08 2008 H1 1 1 PUMP FEED WATER 1 December 2004...
Страница 86: ......