Fault Diagnosis
Depending on whether the fault comes from the outdoor unit or the hydraulic unit, the fault may be indicated by the
digital display or the LED on the interface cards.
►
Faults in the Hydraulic Unit
Faults or breakdowns on the hydraulic unit are indicated by the display on the user interface.
The display shows the
symbol.
Press the
key for more details on the origin of the fault.
When the error has been resolved, the faults are re-initialised at zero automatically.
Before any maintenance operation,
ensure that the general power supply is switched off.
Frost protection is not available when the heat pump is not powered up.
OFF
ON
1
2
U0629273-A
Hydraulic unit: Fault visible on the digital display.
Error
Designation
Probable causes
Proposed actions
10
Outside sensor
Short-circuit.
Unplugged or disconnected sensor.
Faulty sensor.
Other fault.
Check the sensor's wiring.
Replace the sensor.
32
Flow sensor 2
33
Flow sensor HP
44
Return sensor HP
50
DHW sensor 1
60
Room sensor 1
65
Room sensor 2
83
BSB, short circuit
Wiring problem (between the sensor
or remote control, display and
controller).
Check the wiring.
127
Legionella temp
Anti-legionella temp setpoint not
reached.
Check the wiring of the DHW backup /
boiler connection.
212
Internal comm failure
Unplugged or disconnected sensor.
Check the sensor's wiring.
356
Flowmeter
Insufficient flow.
Check the opening of the valves of the
installation.
Check the flowmeter's wiring.
Replace the flowmeter.
369
External
External safety triggered EX3.
-
370
Thermodynamic source
See details
page 74.
-
441
BX31 no function
Short-circuit.
Unplugged or disconnected sensor.
Faulty sensor.
Other fault.
Check the sensor's wiring.
Replace the sensor.
442
BX24 no function
443
BX33 no function
444
BX34 no function
516
Heat pump missing
Loss of connection between
controller and HP.
Check the wiring between X60 and the
interface board.