- 52 -
Line
Function
Setting range
or display
Setting
increment
Basic
setting
Time program heating / cooling, circuit 2
Only with the 2nd circuit kit option.
520
U
Pre-selection (Day / Week)
Mon-Sun, Mon-Fri, Sat-Sun,
Monday, Tuesday, …
Mon-Sun
521
U
1st phase On (start)
00:00... --:--
10 min
6:00
522
U
1st phase Off (end)
00:00... --:--
10 min
22:00
523
U
2nd phase On (start)
00:00... --:--
10 min
--:--
524
U
2nd phase Off (end)
00:00... --:--
10 min
--:--
525
U
3rd phase On (start)
00:00... --:--
10 min
--:--
526
U
3rd phase Off (end)
00:00... --:--
10 min
--:--
536
U
Default values, Circuit 2
No, Yes
No
Yes + OK: The default values memorised in the regulator replace and cancel the customised heating programs.
Your customised settings are therefore lost.
Time program 4 / DHW
If the installation is fitted with the DHW kit.
560
U
Pre-selection (Day / Week)
Mon-Sun, Mon-Fri, Sat-Sun,
Monday, Tuesday, …
Mon-Sun
561
U
1st phase On (start)
00:00... --:--
10 min
00:00
562
U
1st phase Off (end)
00:00... --:--
10 min
05:00
563
U
2nd phase On (start)
00:00... --:--
10 min
14:30
564
U
2nd phase Off (end)
00:00... --:--
10 min
17:00
565
U
3rd phase On (start)
00:00... --:--
10 min
--:--
566
U
3rd phase Off (end)
00:00... --:--
10 min
--:--
576
U
Default values
No, Yes
No
Yes + OK: The default values memorised in the regulator replace and cancel the customised heating programs.
Your customised settings are therefore lost.
Holidays, heating circuit 1 (For the Holiday program is active, the heating mode should be on AUTO).
641
U
Preselection
Period 1 to 8
Period 1
642
U
Period Start (Day / Month)
01.01... 31.12
1
643
U
Period End (Day / Month)
01.01... 31.12
1
648
U
Operating level
Frost protection, Reduced
Frost
protection
Holidays, heating circuit 2 (For the Holiday program is active, the heating mode should be on AUTO).
If the installation consists of 2 heating circuits (Only with the 2nd circuit kit option).
651
U
Preselection
Period 1 to 8
Period 1
652
U
Period Start (Day / Month)
01.01... 31.12
1
653
U
Period End (Day / Month)
01.01... 31.12
1
658
U
Operating level
Frost protection, Reduced
Frost
protection
Waterstage / Installation / 2011 - EN