- 50 -
Controller Menu
▼
General
Only the parameters accessible at the levels:
U
- end user.
I
- Commissioning
S
- Specialist.
are described in this document.
The access levels are specified in the second column of
the table by means of the letters
U, I
and
S
.
The OEM parameters are not described and require a
manufacturer access code.
▼
Setting parameters
-Selecting the desired level.
-Scroll the list of menus.
-Selecting the desired menu.
-Scroll the function lines.
-Selecting the desired line.
-Adjusting the parameter.
-Validate the setting by pressing
OK
.
-To return to the menu, press
ESC
.
If no setting is made for 8 minutes, the screen
automatically returns to the basic display.
OK
Press and release
End user
OK
OK
OK
Time of day and date
Hours / minutes
1
Time
1...24 h
User interface
Day/Month
2
Minutes
0...60 min
Heating circuit 1 timer
programme
Year
3
...
Press for 3
seconds
End user
Start-up
Specialist
OEM
Time of day and date
Hours / minutes
1
User interface
Day/Month
2
Heating circuit 1 timer
programme
Year
3
...
End date of summer time
4
01.01...31.12
End date of summer time
5
▼ Recommended settings for the parameters depending on the installation's emitters
Very Low Temperature
Radiators /
Heating-cooling floor
Low temperature
radiators
Dynamic radiators or
fan-coil heaters
Classic
temperature
radiators
Heating curve
slope
720
(CC1)
1020
(CC2)
0.25 to 0.5
0.5 to 1.25
0.4 to 1.1
1.25 to 3
Curve
displacement
721
(CC1)
1021
(CC2)
0
0
4 *
0
Min.
outgoing value
740
(CC1)
1040
(CC2)
Factory (17 °C)
Factory (17 °C)
30 or 35 °C
Factory
(17 °C)
Max.
initial setpoint
741
(CC1)
1041
(CC2)
50 °C
Factory (55 °C)
65 °C
65 °C
DHW charging
time limitation
5030
Factory (90 min)
Factory (90 min)
40 min
Factory
(90 min)
Waterstage / Installation / 2011 - EN