Cable dimensions and protection rating
These cable dimensions are provided for information purposes only and do not exempt the installer from checking
that these dimensions match requirements and comply with current standards.
•
Outdoor Unit Power Supply
Single phase heat pump
Electricity supply 230 V - 50 Hz
Model
Max. power
consumption
Connection cable
(1)
(phase, neutral, earth)
Circuit breaker
C curve
Waterstage SHP 16
6300 W
3 G 6 mm²
32 A
3 phase heat pump
Electricity supply 400 V - 50 Hz
Model
Maximum power
Connection cable
(1)
(3 phases, neutral, earth)
Circuit breaker
C curve
Waterstage SHP TRI 15
6770 W
5 G 2.5 mm²
20 A
Waterstage SHP TRI 17
7400 W
• Interconnection between outdoor unit and hydraulic unit
The hydraulic unit is powered by the outdoor unit by means of a 4 G 1.5 mm² cable
(phase, neutral, earth, communication bus).
• Electrical backup power supply
The hydraulic unit contains a electrical backup circuit (and a second optional) installed in the storage tank.
Heat pump
Electrical backups
Electrical backup power supply
Model
Power
Nominal
current
Connection cable
(1)
(phase, neutral, earth)
Circuit breaker
C curve
Waterstage SHP 16
2 x 3 kW
26.1 A
3 G 6 mm²
32 A
Waterstage SHP TRI 15
Waterstage SHP TRI 17
9 kW
3 x 13 A
4 G 2.5 mm²
20 A
(1)
Cable type 60245 IEC 57 or 60245 IEC 88.
• DHW power supply (option)
The DHW section is powered directly via a 3 G 1.5 mm² cable (phase, neutral, earth).
Protection by rated circuit breaker (16 A - C curve).