Domestic hot water functions
z
The control sets the DHW temperature, according
to the time program or continuously, to the desired
setpoint. The priority of DHW charging over room
heating is adjustable in this case
The controller has a configurable legionella
function designed for protection against legionella
in the storage tank and the pipes. The circulation
pump is controlled according to the current time
program and operating mode.
Setpoint value
LINE
FUNCTION
1610
Nominal setpoint
1612
Reduced setpoint
The DHW is heated to various setpoint values.
These setpoints are active according to the selected
operating mode and allow the desired temperatures
to be reached in the DHW storage tank.
Reduced setpoint Nominal setpoint
DHW max setpoint
0
10
20
30
40
50
60
70 °C
Important:
For optimal operation we recommend reducing the
setpoints to the lowest value.
Setpoints which are too high may interfere with
heating and cause some discomfort. In this case
DHW/Heating changeover cycles may successively
occur
If DHW charge boosting is not desired during
the day, we recommend adjusting the reduced
temperature setpoint to 15°C. Full charging will
occur during the night at the nominal temperature..
Содержание Waterstage WO*K112LCT
Страница 3: ...1 OUTDOOR UNIT DTW_3SP002E_02 CHAPTER01 2013 2 28 3 PHASE TYPE WO K112LCT WO K140LCT WO K160LCT ...
Страница 30: ...2 HYDRAULIC UNIT DTW_3SP002E_02 CHAPTER02 2013 03 22 3 PHASE TYPE WS K160DC9 ...
Страница 44: ...3 CONTROL SYSTEM DTW_1SP002E_02 CHAPTER03 2013 03 22 WS G140DC6 Hydraulic unit WS K160DC9 Hydraulic unit ...
Страница 125: ... CS01 80 Control system CS01 80 CONTROL SYSTEM CONTROL SYSTEM ...