- (CS01 - 18) -
Control system
- (CS01 - 18) -
C
O
N
TR
O
L
SY
ST
EM
C
O
N
TR
O
L
SY
ST
EM
LINE
ACCESS
LEVEL
FUNCTION
SETTING RANGE
OR DISPLAY
FACTORY
SETTING
8740
U
Room temp 1
0.0…50.0°C
---
Room setpoint 1
4.0…35.0°C
20.0°C
8743
U
Flow temp 1
0.0…140.0°C
---
Flow temp setpoint 1
0.0…140.0°C
---
8756
U
Flow temp cooling 1
0.0…140.0°C
---
Flow temp setpoint cooling 1
0.0…140.0°C
---
8760
I
Heating circuit pump, circuit 2
Off / On
Off
8770
U
Room temp 2
0.0…50.0°C
20.0°C
Room setpoint 2
4.0…35.0°C
20.0°C
8773
U
Flow temp 2
0.0…140.0°C
---
Flow temp setpoint 2
0.0…140.0°C
---
8820
I
DHW pump
Off / On
Off
8821
I
Electric immersion heater DHW
Off / On
Off
8830
U
DHW temp
0.0…140.0°C
0.0°C
DHW temp setpoint
8.0…80.0°C
50.0°C
8840
S
Hours run DHW pump
0…2730h
---
Reset?
Yes / No
Yes
8841
S
Start counter DHW pump
0…2730h
---
Reset?
Yes / No
Yes
8842
S
Hours run electric heater DHW
0…2730h
---
Reset?
Yes / No
Yes
8843
S
Start counter electric heater DHW
0…65535
---
Reset?
Yes / No
Yes
8900
U
Swimming pool temp
0.0…140.0°C
---
Swimming pool setpoint
8.0…80.0°C
22.0°C
8950
S
Common flow temp
0.0…140.0°C
---
Common flow temp setpoint
0.0…140.0°C
---
8957
S
Common flow setpoint refrig
0.0…140.0°C
---
9031
I
Relay output QX1
Off / On
On
9032
I
Relay output QX2
Off / On
On
9033
I
Relay output QX3
Off / On
On
9034
I
Relay output QX4
Off / On
Off
9035
I
Relay output QX5
Off / On
Off
9050
I
Relay output QX21 module 1
Off / On
Off
9051
I
Relay output QX22 module 1
Off / On
Off
9052
I
Relay output QX23 module 1
Off / On
Off
9053
I
Relay output QX21 module 2
Off / On
Off
9054
I
Relay output QX22 module 2
Off / On
Off
9055
I
Relay output QX23 module 2
Off / On
Off
9071
U
Relay output QX31
Off / On
On
9072
U
Relay output QX32
Off / On
On
9073
U
Relay output QX33
Off / On
Off
9074
U
Relay output QX34
Off / On
Off
9075
U
Relay output QX35
Off / On
Off
Содержание Waterstage WO*K112LCT
Страница 3: ...1 OUTDOOR UNIT DTW_3SP002E_02 CHAPTER01 2013 2 28 3 PHASE TYPE WO K112LCT WO K140LCT WO K160LCT ...
Страница 30: ...2 HYDRAULIC UNIT DTW_3SP002E_02 CHAPTER02 2013 03 22 3 PHASE TYPE WS K160DC9 ...
Страница 44: ...3 CONTROL SYSTEM DTW_1SP002E_02 CHAPTER03 2013 03 22 WS G140DC6 Hydraulic unit WS K160DC9 Hydraulic unit ...
Страница 125: ... CS01 80 Control system CS01 80 CONTROL SYSTEM CONTROL SYSTEM ...