Reduced Setpoint Increase
LINE
FUNCTION
HC1
HC2
800
1100
Reduced setpoint increase start
801
1101
Reduced setpoint increase end
This function is used mainly in heating installations
that do not have high supplies of power (e.g. low
power use homes). When outdoor temperatures are
low, adjusting the temperature would take too long.
Increasing the reduced setpoint prevents excessive
cooling of the rooms in order to shorten the
temperature adjustment period when changing over
to the comfort setpoint.
Comfort
setpoint(710)
Start
increase(800)
End increase
(801)
Composite OT
Reduced
setpoint(712)
Mixing Valve Control
LINE
FUNCTION
HC1
HC2
830
1130
Mixer valve boost
834
1134
Actuator running time
Mixer valve boost
The controller adds the increase set here to the
current flow setpoint and uses the result as the
temperature setpoint for the heat generator.
Actuator running time
For the 3-position servomotor, the travel time can
be adjusted. With a 2-position servomotor,
the adjusted travel time is inoperative.
Controlled floor drying function
LINE
FUNCTION
HC1
HC2
850
1150
Floor curing function
851
1151
Floor curing setpoint manually
856
1156
Floor curing day current
857
1157
Floor curing day completed
This function is used in the controlled drying of floors.
It adjusts the flow temperature to a temperature
profile. Drying is performed by floor heating via the
heating circuit with a mixing valve or with a pump.
Содержание Waterstage WO*K112LCT
Страница 3: ...1 OUTDOOR UNIT DTW_3SP002E_02 CHAPTER01 2013 2 28 3 PHASE TYPE WO K112LCT WO K140LCT WO K160LCT ...
Страница 30: ...2 HYDRAULIC UNIT DTW_3SP002E_02 CHAPTER02 2013 03 22 3 PHASE TYPE WS K160DC9 ...
Страница 44: ...3 CONTROL SYSTEM DTW_1SP002E_02 CHAPTER03 2013 03 22 WS G140DC6 Hydraulic unit WS K160DC9 Hydraulic unit ...
Страница 125: ... CS01 80 Control system CS01 80 CONTROL SYSTEM CONTROL SYSTEM ...