5-4
SPARC Enterprise T2000 Server Service Manual • April 2007
FIGURE 5-1
Slide Release Latches
4. While pinching the release latches, slowly pull the server forward until the slide
rails latch.
5.1.4
Removing the Server From a Rack
Remove the server from the rack for all cold-swappable FRU replacement
procedures except the DIMMs, PCI cards, and the system controller.
Caution –
The server weighs approximately 40 lb. (18 kg). Two people are required
to dismount and carry the chassis.
1. Disconnect all the cables and power cords from the server.
2. Extend the server to the maintenance position as described in
“Extending the Server to the Maintenance Position” on page 5-3
3. Press the metal lever (
) that is located on the inner side of the rail to
disconnect the CMA from the rail assembly (on the right side from the back of the
rack).
This action leaves the CMA still attached to the cabinet, but the server chassis is now
disconnected from the CMA.
Содержание SPARC Enterprise T2000
Страница 1: ......
Страница 2: ......
Страница 6: ......
Страница 16: ...xiv SPARC Enterprise T2000 Server Service Manual April 2007 ...
Страница 18: ...xvi SPARC Enterprise T2000 Server Service Manual April 2007 ...
Страница 27: ...Preface xxv Reader s Comment Form ...
Страница 43: ...Chapter 3 Server Diagnostics 3 3 FIGURE 3 1 Diagnostic Flow Chart flowchart ...
Страница 69: ...Chapter 3 Server Diagnostics 3 29 FIGURE 3 10 Flowchart of ALOM CMT Variables for POST Configuration ...
Страница 106: ...4 12 SPARC Enterprise T2000 Server Service Manual April 2007 ...
Страница 152: ...5 46 SPARC Enterprise T2000 Server Service Manual April 2007 ...
Страница 163: ...Appendix A Field Replaceable Units A 3 FIGURE A 2 Field Replaceable Units 2 of 2 13 11 12 10 14 16 15 ...
Страница 173: ......
Страница 174: ......