28
Service Supplement
TX100 S2
Replacement routines
4.1.3
Opening and closing the front bezel
4.1.3.1
Removing the front bezel
The following replacement routines require removing the front bezel:
–
Replacing the front panel cable
–
Replacing the front USB module
Ê
Shut down the server and disconnect the AC power cord from the system.
Ê
You are advised to
–
either bring the server to its upright position
–
or lay the server on its side with the chassis slightly elevated above the
detached front bezel.
Ê
Remove the side cover as described in section
4.1.1.1 on page 23
.
Ê
Remove all accessible drives and dummy covers as described in sections
4.1.5.1 on page 39
and
4.1.6.1 on page 41
.
I
In order to fully remove the front bezel, you first have to disconnect the
front panel cable from the system board and detach it from the cable
cable clamps.
Ê
Open the HDD cage as described in section
4.1.2.1 on page 25
.
Ê
Remove the air duct as described in section
4.1.4.1 on page 33
.
Ê
Remove the front fan module as described in section
4.6.1 on page 72
.