20. OFF DEFROST OPEARTION CONTROL
1. OFF DEFROST OPERATION CONDITION
When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat
exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation
lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost,
and then stop.
In heating operation, the outdoor heat exchanger temperature is less than 25
°F(-4°C)
, and
compressor operation integrating time lasts for more than 30 minutes.
ASU9 / 12RL
OFF Defrost Flow Chart
Heating operation stop
Outdoor heat exchanger temperature:
Below 25
°F(-4°C)
and
Compressor integrating operation:
Over 30 minutes
Defrost start
Defrost Indicater:
[Operation lamp]
7 sec ON / 2 sec OFF
Outdoor heat exchanger temperature:
Over 61
°F(16°C) or
Compressor ON time: Over 15 minutes
Defrost end
2. OFF DEFROST END CONDITION
Release Condition
Outdoor heat exchanger temperature sensor value is higher than
61
°F(16°C)
or Compressor operation time has passed 15 minutes.
05-16
21. MINIMUM
HEAT OPERATION
The MINIMUM
operation functions by pressing
MINIMUM HEAT button on the remote controller.
The MINIMUM
operation is almost the same operation as below settings.
mode HEAT
setting temperature 50
°F(
10
°C)
fan mode AUTO
( Table 16 )
Содержание Inverter Halcyon AOU12RL
Страница 1: ... Manuel d instruction www lutechenergie com ...
Страница 5: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 12: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 33: ...6 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 74: ...8 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 82: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Mar 2009 Printed in Japan ...