Trouble shooting 18
OUTDOOR UNIT Error Method:
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 3 : Check Outdoor Fan
OK
OK
Indicate or Display:
OK
OK
OK
OK
Check Point 1 :
Check connections of Outdoor Unit Electrical Components
Excessive high pressure protection
on cooling
1. Defective connection of electric components 2. Outdoor Fan Operation failure
3. Outdoor Heat Exchanger clogged 4. Thermistor failure 5. EEV failure 6. Main PCB failure
Check if connector is removed.
Check if
the terminal connection
is loose.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
Check Point 2 : Check Outdoor Fan, Heat Exchanger
Is there anything obstructing the air distribution circuit?
Is there any clogging of Outdoor Heat Exchanger?
Is the Fan rotating by hand when operation is off ?
>> If the Fan Motor is locked, replace it.
Check Outdoor Fan Motor. (Refer to Trouble shooting 16)
>> If the Fan Motor is failure, replace it.
Check Thermistor. (Refer to Trouble shooting 5)
>> If the Thermistor is failure, replace it.
Check Point 5 : Check Electronic Expansion Valve
Check Point 4 : Check Thermistor
(PARTS INFORMATION 3)
Check EEV.
Excessive high pressure protection on cooling mode has been
activated.
06-22
Check Point 6 : Replace Main PCB
OK
OK
If Check Point 1 5 do not improve the symptom, change Main PCB.
Outdoor Unit : No indication
Indoor Unit : Operation LED : 7 times, Timer LED : 3 times
ERROR CODE : [E : 24]
Outdoor Unit Main PCB Circuit
Outdoor Fan Motor
Heat Exchanger Temp. Thermistor
Outdoor unit Electronic Expansion Valve
Содержание Inverter Halcyon AOU12RL
Страница 1: ... Manuel d instruction www lutechenergie com ...
Страница 5: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 12: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 33: ...6 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 74: ...8 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 82: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Mar 2009 Printed in Japan ...