3. ANTIFREEZING CONTROL (Cooling and Dry mode)
The compressor frequency is decrease on cooling & dry mode when the indoor heat exchanger
temperature sensor detects the temperature lower than Temperature .
Then, the anti-freezing control is released when it becomes higher than Temperature .
(Table 19 : Anti-freezing Protection Operation / Release Temperature)
4. COOLING PRESSURE OVERRISE PROTECTION
When the outdoor unit heat exchange sensor temperature rises to 153
°F(67°C)
or greater,
the compressor is stopped and trouble display is performed.
5. HIGH TEMPERATURE RELEASE CONTROL ( HEATING MODE )
On heating mode, the compressor frequency is controlled as following based on the
detection value of the indoor heat exchanger temperature sensor.
05-18
Indoor heat exchange
temperature
[ Control System ]
It returns to the normal operation
127°F
(53°C)
122°F
(50°C)
Outdoor temperature
Over than 50
°F(
10
°C)
*1
or
54
°F(12°C)
*2
Less than 50
°F(
10
°C)
*1
or
54
°F(12°C)
*2
*1. When the temperature rises.
*2. When the temperature drops.
39°F(4°C)
45°F(7°C)
55°F(13°C)
Temperature
Temperature
The compressor frequency is
decreased 3Hz every 60seconds.
Содержание Inverter Halcyon AOU12RL
Страница 1: ... Manuel d instruction www lutechenergie com ...
Страница 5: ...1 SPECIFICATIONS R410A WALL MOUNTED type INVERTER ...
Страница 8: ...2 DIMENSIONS R410A WALL MOUNTED type INVERTER ...
Страница 10: ...3 REFRIGERANT SYSTEM DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 12: ...4 CIRCUIT DIAGRAM R410A WALL MOUNTED type INVERTER ...
Страница 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A WALL MOUNTED type INVERTER ...
Страница 33: ...6 TROUBLE SHOOTING R410A WALL MOUNTED type INVERTER ...
Страница 74: ...8 REPLACEMENT PARTS R410A WALL MOUNTED type INVERTER ...
Страница 82: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan Mar 2009 Printed in Japan ...