14-2. Error code
If an error occurs, the LED will light up to display the error location and the error code.
¢
Error display mode
Display when an error occurs.
POWER
ERROR
PUMP
DOWN
LOW
NOISE
PEAK
CUT
MODE
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
●
Blink
(Hi speed)
○
○
○
○
○
○
Sign “
○
”: Lights off, “
●
”: Lights on
NOTE:
Check that the “ERROR” LED blinks, then press the [ENTER] button once.
¢
Error code check table
LED display
Remark
Description
POWER/
MODE
ERROR
PUMP DOWN
LOW NOISE
PEAK CUT
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
(2)
●
(1)
(1)
○
○
●
●
Serial communication error
Serial forward transmission error immediately after
operation
(2)
●
(1)
(1)
○
●
○
○
Serial forward transmission error during operation
(2)
●
(2)
(2)
○
○
○
●
Indoor unit capacity error
Indoor unit capacity error
(2)
●
(5)
(15)
○
○
○
●
Indoor unit error
Indoor unit error
(2)
●
(6)
(2)
○
○
○
●
Outdoor unit main PCB error
Outdoor unit PCB model information error
(2)
●
(6)
(3)
○
○
○
●
Inverter PCB error
Inverter error
(2)
●
(6)
(5)
○
○
●
●
r
o
r
r
e
L
l
a
n
i
m
r
e
t
p
i
r
T
r
o
r
r
e
M
P
I
(2)
●
(7)
(1)
○
○
○
●
Discharge temp. sensor error
Discharge temp. sensor 1 error
(2)
●
(7)
(2)
○
○
○
●
Compressor temp. sensor error
Compressor temp. sensor 1 error
(2)
●
(7)
(3)
○
○
●
○
Outdoor unit Heat Ex. sensor error
Heat Ex. middle temp. sensor error
(2)
●
(7)
(3)
○
○
●
●
Outdoor unit Heat Ex. liquid temp. sensor error
(2)
●
(7)
(4)
○
○
○
●
Outdoor temp. sensor error
Outdoor temp. sensor error
(2)
●
(7)
(7)
○
○
○
●
Heat sink temp. sensor error
Heat sink temp. sensor error
(2)
●
(8)
(4)
○
○
○
●
Current sensor error
Current sensor 1 error (stoppage permanently)
(2)
●
(8)
(6)
○
●
○
○
Pressure sensor error
High pressure switch 1 error
(2)
●
(8)
(6)
○
○
○
●
Outdoor unit discharge pressure sensor error
(2)
●
(8)
(6)
○
○
●
●
Outdoor unit suction pressure sensor error
(2)
●
(9)
(4)
○
○
○
●
n
o
i
t
c
e
t
e
d
p
i
r
T
n
o
i
t
c
e
t
e
d
p
i
r
T
(2)
●
(9)
(5)
○
○
○
●
Compressor motor control error
Rotor position detection error (stoppage permanently)
(2)
●
(9)
(7)
○
○
●
●
Outdoor unit fan motor 1 error
Duty error
(2)
●
(9)
(8)
○
○
●
●
Outdoor unit fan motor 2 error
Duty error
(2)
●
(9)
(9)
○
○
○
●
4-way valve error
4-way valve error
(2)
●
(10)
(1)
○
○
○
●
Discharge temp. 1 error
Discharge temp. 1 error
(2)
●
(10)
(3)
○
○
○
●
Compressor temp. error
Compressor 1 temp. error
(2)
●
(10)
(5)
○
○
○
●
Pressure error 2
Low pressure error
Display mode
: Lights on
: Lights off
: Blink (0.5s Lights on / 0.5s Lights off)
( ) : Number of ashing
DESIGN & TECHNICAL MANUAL
- 80 -
OUTDOOR UNIT
AOHG72-90LRLA
Содержание GENERAL ARHG72LHTA
Страница 5: ...Part 1 INDOOR UNIT DUCT TYPE ARHG72LHTA ARHG90LHTA ...
Страница 11: ...4 Wiring diagrams 4 1 Model ARHG72LHTA I O PCB WLAN adapter Converter etc 7 DUCT TYPE ARHG72 90LHTA ...
Страница 12: ...4 2 Model ARHG90LHTA I O PCB WLAN adapter Converter etc 8 DUCT TYPE ARHG72 90LHTA ...
Страница 57: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOHG72LRLA AOHG90LRLA ...
Страница 64: ...5 Wiring diagrams 5 1 Models AOHG72LRLA and AOHG90LRLA 60 OUTDOOR UNIT AOHG72 90LRLA ...