When function setting is "Forced stop" mode
• In the case of "Edge" input
Function
setting /
Rotary SW of
External input and
output PCB
External input
Input signal
Command
46-02
-
Input of indoor unit
Terminal
Off → On
Forced stop
On → Off
Normal
60-00 / 1
External input and
output PCB
Input 1
Off → On
Forced stop
On → Off
Normal
On
Off
Forced stop
Normal
Operation
Stop
Remote controller
On
On
Indoor unit
On
Input
• In the case of "Pulse" input
Function
setting /
Rotary SW of
External input and
output PCB
External input
Input signal
Command
46-02
60-00 / 1
External input and
output PCB
Input 1
Pulse
Forced stop
Input 2
Pulse
Normal
On
Off
Operation
Stop
Remote controller
On
Off
Forced stop
Normal
Input 1
Input 2
On
On
On
Indoor unit
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the
remote controller is restricted.
• When forced stop function is used with forming a remote controller group, connect the
same equipment to each indoor unit within the group.
- 27 -
DUCT TYPE
ARHG72-90LHTA
Содержание GENERAL ARHG72LHTA
Страница 5: ...Part 1 INDOOR UNIT DUCT TYPE ARHG72LHTA ARHG90LHTA ...
Страница 11: ...4 Wiring diagrams 4 1 Model ARHG72LHTA I O PCB WLAN adapter Converter etc 7 DUCT TYPE ARHG72 90LHTA ...
Страница 12: ...4 2 Model ARHG90LHTA I O PCB WLAN adapter Converter etc 8 DUCT TYPE ARHG72 90LHTA ...
Страница 57: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOHG72LRLA AOHG90LRLA ...
Страница 64: ...5 Wiring diagrams 5 1 Models AOHG72LRLA and AOHG90LRLA 60 OUTDOOR UNIT AOHG72 90LRLA ...