LED lamp
Function or operation method
(1) POWER/MODE
Green
Lights on while power on.
Local setting in outdoor unit or error code is displayed with blink.
(2) ERROR
Red
Blinks during error operation.
(3) PUMP DOWN (L1)
Orange Lights on during pump down operation.
(4)
LOW NOISE MODE
(L2 and L3)
Orange
Lights on during “Low noise mode” when local setting is activated.
(Lighting pattern of L2 and L3 indicates low noise level.)
(5)
PEAK CUT MODE
(L4, L5, and L6)
Orange
Lights on during “Peak cut mode” when local setting is activated.
(Lighting pattern of L4, L5, and L6 indicates peak cut level.)
Switch button
Function or operation method
SW107
MODE
Switches between “Local setting” and “Error code display”.
SW108
SELECT
Switches between the individual “Local settings” and the “Error code displays”.
SW109
ENTER
Switches between the individual “Local settings” and the “Error code displays”.
SW112
EXIT
Returns to “Operation status display”.
SW110
PUMP DOWN Starts the pump down operation.
¢
Function setting table
No.
Setting item
LED display
Factory
setting
POWER
MODE
ERROR
PUMP
DOWN
LOW NOISE
PEAK CUT
(L1)
(L2)
(L3)
(L4)
(L5)
(L6)
1
Low noise
mode setting
Level 1
Blink
(9 times)
○
○
○
●
○
○
●
♦
Level 2
○
○
○
●
○
●
○
2
Peak cut
mode setting
Level 1
○
○
●
○
○
○
●
Level 2
○
○
●
○
○
●
○
Level 3
○
○
●
○
○
●
●
Level 4
○
○
●
○
●
○
○
♦
Sign "○": Lights off, "●": Lights on
No.
Setting item
Content
1
Low noise mode setting
By using the "Low noise mode", the limit of the noise level will be set to
decrease the noise level. The mode comes in 2 levels which can be set
accordingly.
To turn on the mode, use the external input terminal (CN131).
• By using this mode, the cooling/heating performance may decrease.
• Depending on the operating condition, the noise level may not decrease even
if the Low noise mode is on.
2
Peak cut mode setting
The capacity limit can be selected when operating with the “Peak Cut mode.”
The operation selection can be done by external input terminal (CN132).
The lower the level, the more the effect of energy saving, but the cooling/
heating performance decreases.
•
Noise level as low noise mode setting
Unit: dB (A)
AOHG72LRLA
AOHG90LRLA
Cooling
Heating
Cooling
Heating
Level1
53
53
53
55
Level2
51
51
51
53
DESIGN & TECHNICAL MANUAL
- 74 -
OUTDOOR UNIT
AOHG72-90LRLA
Содержание GENERAL ARHG72LHTA
Страница 5: ...Part 1 INDOOR UNIT DUCT TYPE ARHG72LHTA ARHG90LHTA ...
Страница 11: ...4 Wiring diagrams 4 1 Model ARHG72LHTA I O PCB WLAN adapter Converter etc 7 DUCT TYPE ARHG72 90LHTA ...
Страница 12: ...4 2 Model ARHG90LHTA I O PCB WLAN adapter Converter etc 8 DUCT TYPE ARHG72 90LHTA ...
Страница 57: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOHG72LRLA AOHG90LRLA ...
Страница 64: ...5 Wiring diagrams 5 1 Models AOHG72LRLA and AOHG90LRLA 60 OUTDOOR UNIT AOHG72 90LRLA ...