11) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function number
Setting value
Setting description
Factory setting
49
00
Disable
01
Enable
02
Remote controller
♦
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the set-
ting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low
speed.
02: Enable or disable this function by remote controller setting.
NOTES:
• As the factory setting, this setting is initially inactivated.
• Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for
energy saving function or connecting a network converter.
To confirm if the remote controller has this setting, refer to the operating manual of each re-
mote controller.
12) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and
output”.
Function number
Setting value
Setting description
Factory setting
60
00
Operation status
♦
01—08
(Setting prohibited)
09
Error status
10
Indoor unit fan operation status
11
External heater
- 47 -
DUCT TYPE
ARHG72-90LHTA
Содержание GENERAL ARHG72LHTA
Страница 5: ...Part 1 INDOOR UNIT DUCT TYPE ARHG72LHTA ARHG90LHTA ...
Страница 11: ...4 Wiring diagrams 4 1 Model ARHG72LHTA I O PCB WLAN adapter Converter etc 7 DUCT TYPE ARHG72 90LHTA ...
Страница 12: ...4 2 Model ARHG90LHTA I O PCB WLAN adapter Converter etc 8 DUCT TYPE ARHG72 90LHTA ...
Страница 57: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOHG72LRLA AOHG90LRLA ...
Страница 64: ...5 Wiring diagrams 5 1 Models AOHG72LRLA and AOHG90LRLA 60 OUTDOOR UNIT AOHG72 90LRLA ...