When function setting is "Operation/Stop" mode 2
• In the case of "Edge" input
Function
setting /
Rotary SW of
External input and
output PCB
External input
Input signal Command
46-03
-
Input of indoor unit
Terminal
Off → On
Operation
On → Off
Stop (R.C.
disabled)
60-00 / 1
External input and
output PCB
Input 1
Off → On
Operation
On → Off
Stop (R.C.
disabled)
On
Input
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote controller
On
On
Off
• In the case of "Pulse" input
Function
setting /
Rotary SW of
External input and
output PCB
External input
Input signal Command
46-03
60-00 / 1
External input and
output PCB
Input 1
Pulse
Operation
Input 2
Pulse
Stop (R.C.
disabled)
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
Input 1
Input 2
(R.C. disabled)
Off
On
NOTES:
• When "Operation/Stop" mode 2 function is used with forming a remote controller group,
connect the same equipment to each indoor unit within the group.
DESIGN & TECHNICAL MANUAL
- 28 -
DUCT TYPE
ARHG72-90LHTA
Содержание GENERAL ARHG72LHTA
Страница 5: ...Part 1 INDOOR UNIT DUCT TYPE ARHG72LHTA ARHG90LHTA ...
Страница 11: ...4 Wiring diagrams 4 1 Model ARHG72LHTA I O PCB WLAN adapter Converter etc 7 DUCT TYPE ARHG72 90LHTA ...
Страница 12: ...4 2 Model ARHG90LHTA I O PCB WLAN adapter Converter etc 8 DUCT TYPE ARHG72 90LHTA ...
Страница 57: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOHG72LRLA AOHG90LRLA ...
Страница 64: ...5 Wiring diagrams 5 1 Models AOHG72LRLA and AOHG90LRLA 60 OUTDOOR UNIT AOHG72 90LRLA ...