1-5. Rotation number of compressor limitation by outdoor
temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
•
Cooling/Dry mode
F zone
13°C
E zone
7°C
D zone
°C
C zone
B zone
A zone
-5
2
°C
-10°C
G zone
21°C
J zone
50°C
K zone
52°C
H zone
31°C
I zone
46°C
Model name
Outdoor temperature zone
Limitation of compressor
frequency
AOHG45KRTA
AOHG54KRTA
A zone
50 rps
B zone
47 rps
C zone
40 rps
D zone
30 rps
E zone
22 rps
F zone
20 rps
G zone
16 rps
H zone
16 rps
I zone
17 rps
J zone
23 rps
K zone
28 rps