
2-10. E: 63. Inverter error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: 63
Detective actuator
Outdoor unit
Inverter PCB
Error information received from inverter PCB
Forecast of cause
External cause
Power supply to inverter PCB wiring disconnection or
open
Inverter PCB failure
Check point 1. Turn the power on again?
Error displayed again?
↓
Check point 2. Check the wiring (power supply to inverter PCB)
•
Connector and wiring connection state check
•
Cable open check
↓
Check point 3. Replace inverter PCB
Replace inverter PCB
↓
End
Check point 1-2. Check external cause
•
Check if temporary voltage drop was not generated.
•
Check if momentary open was not generated.
•
Check if ground is connection correctly or there are no related cables near the power line.
↓
End
2-10. E: 63. Inverter error (Outdoor unit)
- (03-16) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание General AOHG45KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 01 24 SR_CH01_AR040EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 04 07 SR_CH02_AR040EG_02 ...
Страница 33: ...3 TROUBLESHOOTING 2022 04 07 SR_CH03_AR040EG_02 ...
Страница 36: ......
Страница 93: ...4 CONTROL AND FUNCTIONS 2022 02 04 SR_CH04_AR040EG_01 ...
Страница 127: ...5 FILED WORKING 2022 04 07 SR_CH05_AR040EG_02 ...