7-8. High temperature and high pressure release control
The compressor is controlled as follows.
•
Cooling mode
Indoor unit heat exchanger
temperature rises
Indoor unit heat exchanger
temperature drops
Stable zone
AB
BC
CD
Zone A
Zone B
Zone C
Zone D
AB:
64°C
BC:
60°C
CD:
58°C
Zone
Operation
Zone A
Compressor is stopped.
Zone B
The compressor frequency is decreased.
-7 rps/120 sec.
Zone C
The protection is released and the operation is returned to normal mode.
Zone D
•
Heating mode
Indoor unit heat exchanger
temperature rises
Indoor unit heat exchanger
temperature drops
Stable zone
AB
BC
CD
DE
Zone A
Zone B
Zone C
Zone D
Zone E
AB:
63°C
BC:
53°C
CD:
50°C
DE:
48°C
Zone
Operation
Zone A
Compressor is stopped.
Zone B
The compressor frequency is decreased.
-7 rps/120 sec.
Zone C
-1 rps/120 sec.
Zone D
The protection is released and the operation is returned to normal mode.
Zone E
7-8. High temperature and high pressure release control
- (04-31) -
7. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание General AOHG45KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 01 24 SR_CH01_AR040EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 04 07 SR_CH02_AR040EG_02 ...
Страница 33: ...3 TROUBLESHOOTING 2022 04 07 SR_CH03_AR040EG_02 ...
Страница 36: ......
Страница 93: ...4 CONTROL AND FUNCTIONS 2022 02 04 SR_CH04_AR040EG_01 ...
Страница 127: ...5 FILED WORKING 2022 04 07 SR_CH05_AR040EG_02 ...