Peak cut mode
By performing following on-site work, operation that suppresses the current value can be enabled:
The air conditioner is set to the “Peak cut mode” when closing the contact input of a commercial
timer or on/off switch to a connector on the control PCB of the outdoor unit.
•
Circuit diagram example
Outdoor unit
control PCB
Connected unit
(Locally purchased)
Example: Switch
Signal
10m*
Connector
1
2
1
2
P5
8
0
P
A5
8
0
•
Contact capacity: DC 24 V or more, 10 mA
or more.
•
*: Make the distance from the PCB to the
connected unit within 10 m.
•
Construct a circuit as shown in this figure
with using optional parts mentioned below.
•
Input signal: On in “Peak cut mode”
•
Input signal: Off in normal operation
•
To set the level of “Peak cut mode”, refer
to “Peak cut mode” in
On
Off
On
Off
Input signal
Peak cut mode
•
Optional part
Part name
Model name
Exterior
External connect kit
UTY-XWZXZ3
External input wire
4-1. External input
- (05-24) -
4. External input and output (For outdoor unit)
FIELD
WORKING
FIELD
WORKING
Содержание General AOHG45KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 01 24 SR_CH01_AR040EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 04 07 SR_CH02_AR040EG_02 ...
Страница 33: ...3 TROUBLESHOOTING 2022 04 07 SR_CH03_AR040EG_02 ...
Страница 36: ......
Страница 93: ...4 CONTROL AND FUNCTIONS 2022 02 04 SR_CH04_AR040EG_01 ...
Страница 127: ...5 FILED WORKING 2022 04 07 SR_CH05_AR040EG_02 ...