Available Sensor ID
Sensor ID
Item
Unit
Remarks
01
112
Compressor total cooling operation
hours
11: h
01
113
Compressor total operation hours
11: h
01
114
Outdoor unit fan 1 total operation
hours
11: h
01
115
Outdoor unit fan 2 total operating
hours
11: h
01
145
Outdoor low noise input (External
input)
00: —
0: Off, 1: On
01
146
Outdoor peak cut (External input)
00: —
0: Off
1: Mode 4 (100%)
2: Mode 3 (75%)
3: Mode 2 (50%)
4: Mode 1 (Forced thermostat off)
01
147
Demand response (External input)
00: —
0: Normal, 1: DRM1, 2: DRM2, 3:
DRM3
01
148
Switching cooling and heating mode
(External input)
00: —
0: Cooling, 1: Heating
01
149
Emergency stop (External input)
00: —
0: Off, 1: On
01
155
Compressor status (External output)
00: —
0: Off, 1: On
01
156
Error status (External output)
00: —
0: Off, 1: On
6-13. Unit status monitoring and the detected value indication
- (04-27) -
6. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание General AOHG45KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2022 01 24 SR_CH01_AR040EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2022 04 07 SR_CH02_AR040EG_02 ...
Страница 33: ...3 TROUBLESHOOTING 2022 04 07 SR_CH03_AR040EG_02 ...
Страница 36: ......
Страница 93: ...4 CONTROL AND FUNCTIONS 2022 02 04 SR_CH04_AR040EG_01 ...
Страница 127: ...5 FILED WORKING 2022 04 07 SR_CH05_AR040EG_02 ...