Compressor status output
Signal on compressor operation status is generated when the compressor is running.
•
Circuit diagram example
Outdoor unit
control PCB
Example:
Relay unit
Connected unit (Locally purchased)
Example: Fan
Signal
Connector
1
2
1
2
10m*
12 V
On/
Off
P5
9
0
On/
Off
P
A5
9
0
•
Output voltage (Vcc): DC 12
V 50 mA or less
•
*: Make the distance from
the PCB to the connected
unit within 10 m.
Operation
Stop
On
Off
Compressor
status
Output signal
•
Optional part
Part name
Model name
Exterior
External connect kit
UTY-XWZXZ3
External output wire
4-2. External output
- (05-26) -
4. External input and output (For outdoor unit)