(The above resistance value is a typical value. There is some distribution. A
Trouble Shooting of Refrigerant Cycle
[Diagnosis Table for Defective Component]
: Item of most possible cause
IPM Protection
Compressor
Location error
Discharge
Temperature Error
Cooling High
Pressure
Protection
Refrigerant
leak
Compressor failure(*)
EEV failure (*)
Thermistor failure (*)
(*) Trouble Shooting Method
(1) Checking method of the compressor failure
Insert the AC plug and start up the cooling operation. Input Test operation signal and check if the
compressor operates.
If it does not operate, measure the resistance value of compressor windings between U-V, V-W,
W-U.
If any of the resistance value between U-V, V-W, W-U is not same as others, the compressor is
defective.
Compressor Failure
NORMAL
AW * Z24LBC
Compressor Case Temperature at 25°C: 1.086 ohm
s it also changes by the
compressor temperature, the measured value may be much different from the above table when
measured right after stopping operation.)
(2) Checking method of EEV failure
- Insert the AC plug and start up the operation. Check if the EEV operates just before compressor is turned
on. (Touch EEV by hand and check it.)
If it does not operate, check if the coil or connector of EEV is removed or loose.
If it operates, check the discharge thermistor / outdoor heat exchanger thermistor / indoor heat
exchanger thermistor. (Refer to (3) for checking method.)
(3) Checking method of Thermistor
- Check each thermistor if it is removed or the connector is loose.
If there is no problem, remove the connector of the thermistor from the PCB and check the resistance
value (refer to the thermitor characteristics table).
07-10
Содержание AW?Z24LBC
Страница 4: ...1 SPECIFICATIONS R410A CEILING WALL type INVERTER ...
Страница 6: ...2 DIMENSIONS R410A CEILING WALL type INVERTER ...
Страница 7: ... Unit mm DIMENSIONS INDOOR UNIT 02 01 Models AW Z24LBC 300 298 899 250 170 40 ...
Страница 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CEILING WALL type INVERTER ...
Страница 11: ...4 CIRCUIT DIAGRAM R410A CEILING WALL type INVERTER ...
Страница 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CEILING WALL type INVERTER ...
Страница 36: ...6 REFRIGERANT CAUTION R410A R410A CEILING WALL type INVERTER ...
Страница 53: ...IPM Protection Checking Points Check the following points and locate the cause in the outdoor unit Cause ...
Страница 63: ...9 REPLACEMENT PARTS R410A CEILING WALL type INVERTER ...
Страница 64: ...REPLACEMENT PARTS 09 01 Models AW Z24LBC ...
Страница 65: ...REPLACEMENT PARTS 09 02 Models AW Z24LBC ...
Страница 66: ...REPLACEMENT PARTS 09 03 Models AW Z24LBC ...
Страница 67: ...REPLACEMENT PARTS 09 04 Models AO Z24LBT ...
Страница 68: ...REPLACEMENT PARTS 09 05 Models AO Z24LBT ...
Страница 91: ...REPLACEMENT PARTS 09 28 PROCESS Wiring ...
Страница 92: ...REPLACEMENT PARTS 09 29 PROCESS Wiring ...
Страница 93: ...REPLACEMENT PARTS 09 30 Model AO Z24LBT PROCESS Wiring ...
Страница 94: ...10 INSTALLATION MANUAL R410A CEILING WALL type INVERTER ...
Страница 97: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan FEB 2007 Printed in Japan ...