Self - diagnosis function and Checking points
Error Indication
Operation
(RED)
Timer
(GREEN)
Error
(Protection)
Diagnosis Method
0.5 sec
2 times
The indoor fan speed is 1/3 of the target frequency after 56 seconds from starting operation or from the time the fan mode was
changed. > Operation stop. (It releases by sending the operation stop signal from the remote controller).
The discharge temperature error is activated.
> Permanent stop.
0.5 sec
6 times
07-06
Excessive high pressure
protection on cooling
Discharge temperature
error
Indoor fan speed error
Indoor fan lock error
The indoor fan speed is 0 rpm after 56 seconds from starting operation or from the time the fan mode was changed.
> Operation stop. (It releases by sending the operation stop signal from the remote controller).
[Diagnosis Point]
Fan motor connector loose /defective contact.
Fan motor defective
Controller PCB defective.
[Diagnosis Point]
Fan motor connector loose /defective contact.
Fan motor defective
Controller PCB defective.
[Diagnosis Point]
Check if 2-way valve or 3-way valve is left open.
Heat radiation is blocked (Inlet /outlet).
Check if outdoor fan is defective (does not rotate).
Refrigeration cycle defective (Refer to after mentioned "refrigerant cycle diagnosis").
Excessive high pressure protection on cooling mode has been activated.
> Compressor, outdoor fan : Off (It releases after 3 minute ST).
[Diagnosis Point]
Heat radiation is blocked (Inlet /outlet).
Check if outdoor fan is defective (does not rotate).
Refrigeration cycle defective (Refer to after mentioned "refrigerant cycle diagnosis").
Excessive voltage of DC voltage on PFC circuit in inverter PCB is detected, or the excessive current in the circuit is detected
.
> Permanent stop.
Active Filter error or instantaneous cut off error is detected.
> Compressor, Outdoor Fan : OFF.
[Diagnosis Point]
Controller PCB defective (Refer to after mentioned "PFC circuit diagnosis")
PFC circuit error
0.5 sec
3 times
0.5 sec
2 times
0.5 sec
3 times
0.5 sec
2 times
Active Filter error
0.5 sec
3 times
0.5 sec
7 times
[Diagnosis Point]
<CAUTION> Even if the unit is normal, it may detect error depending on the power supply voltage condition.
Controller PCB defective (Refer to after mentioned "Active Filter diagnosis")
Check the wiring connection (Connector is loose/open, Choke coil)
0.5 sec
8 times
0.5 sec
5 times
Pressure Switch Error
If the pressure switch is open for 10 sec. when the power is turned on
> Compressor, Outdoor Fan : OFF
When it becomes normal after 10 sec. passed, the openretion is resumed based
on serial forward transfor signal.
[Diagnosis Point]
Check interruption (Air intake / outlet)
Check outdoor fan operation (does not rotate)
Check refrigerant cycle (Refer to "Refrigerant cycle diagnosis" which is described in the later chapter)
Содержание AW?Z24LBC
Страница 4: ...1 SPECIFICATIONS R410A CEILING WALL type INVERTER ...
Страница 6: ...2 DIMENSIONS R410A CEILING WALL type INVERTER ...
Страница 7: ... Unit mm DIMENSIONS INDOOR UNIT 02 01 Models AW Z24LBC 300 298 899 250 170 40 ...
Страница 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CEILING WALL type INVERTER ...
Страница 11: ...4 CIRCUIT DIAGRAM R410A CEILING WALL type INVERTER ...
Страница 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CEILING WALL type INVERTER ...
Страница 36: ...6 REFRIGERANT CAUTION R410A R410A CEILING WALL type INVERTER ...
Страница 53: ...IPM Protection Checking Points Check the following points and locate the cause in the outdoor unit Cause ...
Страница 63: ...9 REPLACEMENT PARTS R410A CEILING WALL type INVERTER ...
Страница 64: ...REPLACEMENT PARTS 09 01 Models AW Z24LBC ...
Страница 65: ...REPLACEMENT PARTS 09 02 Models AW Z24LBC ...
Страница 66: ...REPLACEMENT PARTS 09 03 Models AW Z24LBC ...
Страница 67: ...REPLACEMENT PARTS 09 04 Models AO Z24LBT ...
Страница 68: ...REPLACEMENT PARTS 09 05 Models AO Z24LBT ...
Страница 91: ...REPLACEMENT PARTS 09 28 PROCESS Wiring ...
Страница 92: ...REPLACEMENT PARTS 09 29 PROCESS Wiring ...
Страница 93: ...REPLACEMENT PARTS 09 30 Model AO Z24LBT PROCESS Wiring ...
Страница 94: ...10 INSTALLATION MANUAL R410A CEILING WALL type INVERTER ...
Страница 97: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan FEB 2007 Printed in Japan ...