2. HEATING OPERATION
2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower by 3°C than a set temperature, the compressor operation
frequency will attain to maximum performance.
* If the room temperature is higher 2.5°C than a set temperatire, the compressor will be
stopped.
minimum
frequency
maximum
frequency
AW * Z24LBC
21Hz
87Hz
Outside air Outside air
temperature temperature
19°C
C zone
17°C
14°C
B zone
12°C
A zone
Hi
Me
Lo
Quiet
A zone
87Hz
63Hz
51Hz
49Hz
B zone
87Hz
63Hz
51Hz
47Hz
24LBC
C zone
87Hz
63Hz
51Hz
43Hz
S-Quiet
47Hz
43Hz
39Hz
* When the room temperature is b2°C to -3°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table2.
However, the maximum frequency is limited in the range shown in Figure 2 based on the
fan speed mode and the outdoor temperature.
( Table 2 : Compressor Frequency Range )
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
* The room temperature is controlled 2°C higher than the setting temperature for 60 minutes
after starting the operation.
After 60 minutes, it is controlled based on the normal setting temperature.
05-02
Содержание AW?Z24LBC
Страница 4: ...1 SPECIFICATIONS R410A CEILING WALL type INVERTER ...
Страница 6: ...2 DIMENSIONS R410A CEILING WALL type INVERTER ...
Страница 7: ... Unit mm DIMENSIONS INDOOR UNIT 02 01 Models AW Z24LBC 300 298 899 250 170 40 ...
Страница 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CEILING WALL type INVERTER ...
Страница 11: ...4 CIRCUIT DIAGRAM R410A CEILING WALL type INVERTER ...
Страница 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CEILING WALL type INVERTER ...
Страница 36: ...6 REFRIGERANT CAUTION R410A R410A CEILING WALL type INVERTER ...
Страница 53: ...IPM Protection Checking Points Check the following points and locate the cause in the outdoor unit Cause ...
Страница 63: ...9 REPLACEMENT PARTS R410A CEILING WALL type INVERTER ...
Страница 64: ...REPLACEMENT PARTS 09 01 Models AW Z24LBC ...
Страница 65: ...REPLACEMENT PARTS 09 02 Models AW Z24LBC ...
Страница 66: ...REPLACEMENT PARTS 09 03 Models AW Z24LBC ...
Страница 67: ...REPLACEMENT PARTS 09 04 Models AO Z24LBT ...
Страница 68: ...REPLACEMENT PARTS 09 05 Models AO Z24LBT ...
Страница 91: ...REPLACEMENT PARTS 09 28 PROCESS Wiring ...
Страница 92: ...REPLACEMENT PARTS 09 29 PROCESS Wiring ...
Страница 93: ...REPLACEMENT PARTS 09 30 Model AO Z24LBT PROCESS Wiring ...
Страница 94: ...10 INSTALLATION MANUAL R410A CEILING WALL type INVERTER ...
Страница 97: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan FEB 2007 Printed in Japan ...