22. VARIOUS PROTECTIONS
(1). DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL
The discharge gas thermosensor (discharge thermistor : Outdoor side) will detect discharge gas
temperature.
AW * Z24LBC
104°C
101°C
110°C
AW * Z24LBC
AW * Z24LBC
7.0A / 6.5A
9.5A / 9.0A
11.5A /11.0A
When the discharge temperature becomes higher than Temperature ,the compressor frequency
is decreased 20 Hz, and it continues to decrease the frequency for 20 Hz every 120 seconds until
the temperature becomes lower than Temperature .
When the discharge temperature becomes lower than Temperature ,the control of the control of the
compressor frequency is released.
When the discharge temperature becomes higher than Temperature ,the compressor is stopped
and the indoor unit LED starts blinking.
(Table 15 : Discharge Temperature Over Rise Prevension Control / Release Temperature)
Temperature
Temperature
Temperature
(2). CURRENT RELEASE CONTROL
The compressor frequency is controlled so that the outdoor unit input current does not exceeds
the current limit velue that was set up with the outdoor temperature.
The compressor frequency returns to the designated frequency of the indoor unit at the time
when the frequency becomes lower than the release value.
(Table 16 : Current Release Operation Value / Release Value)
[ Cooling / Dry ]
OT : Outdoor Temperature
OT : Outdoor Temperature
05-19
10.5A / 10.0A
13.0A / 12.5A
15.0A / 14.5A
17.0A / 16.5A
OT (Control / Release)
17°C
12°C
5°C
46°C
40°C
OT (Control / Release)
[ Heating ]
Содержание AW?Z24LBC
Страница 4: ...1 SPECIFICATIONS R410A CEILING WALL type INVERTER ...
Страница 6: ...2 DIMENSIONS R410A CEILING WALL type INVERTER ...
Страница 7: ... Unit mm DIMENSIONS INDOOR UNIT 02 01 Models AW Z24LBC 300 298 899 250 170 40 ...
Страница 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CEILING WALL type INVERTER ...
Страница 11: ...4 CIRCUIT DIAGRAM R410A CEILING WALL type INVERTER ...
Страница 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CEILING WALL type INVERTER ...
Страница 36: ...6 REFRIGERANT CAUTION R410A R410A CEILING WALL type INVERTER ...
Страница 53: ...IPM Protection Checking Points Check the following points and locate the cause in the outdoor unit Cause ...
Страница 63: ...9 REPLACEMENT PARTS R410A CEILING WALL type INVERTER ...
Страница 64: ...REPLACEMENT PARTS 09 01 Models AW Z24LBC ...
Страница 65: ...REPLACEMENT PARTS 09 02 Models AW Z24LBC ...
Страница 66: ...REPLACEMENT PARTS 09 03 Models AW Z24LBC ...
Страница 67: ...REPLACEMENT PARTS 09 04 Models AO Z24LBT ...
Страница 68: ...REPLACEMENT PARTS 09 05 Models AO Z24LBT ...
Страница 91: ...REPLACEMENT PARTS 09 28 PROCESS Wiring ...
Страница 92: ...REPLACEMENT PARTS 09 29 PROCESS Wiring ...
Страница 93: ...REPLACEMENT PARTS 09 30 Model AO Z24LBT PROCESS Wiring ...
Страница 94: ...10 INSTALLATION MANUAL R410A CEILING WALL type INVERTER ...
Страница 97: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan FEB 2007 Printed in Japan ...