Self - diagnosis function and Checking points
Error Indication
Operation
(RED)
Timer
(GREEN)
Error
(Protection)
Diagnosis Method
Abnormal current value of IPM is detected.
> Permanent stop.
07-05
CT error
IPM protection
[Diagnosis Point]
Heat radiation is blocked (inlet/outlet).
Check if outdoor fan is defective (does not rotate).
Controller PCB defective (Refer to after mentioned "IPM diagnosis").
Refrigeration cycle defective (Refer to after mentioned "refrigeration cycle diagnosis").
The current value during the operation after 1 minute from starting up the compressor is 0A.
> permanent stop.
[Diagnosis Point]
Check if CT wire is open.
Controller PCB defective.
The compressor speed does not synchronize with the control signal. (Including start up failure of the compressor).
> permanent stop.
[Diagnosis Point]
Check if 2-way valve or 3-way valve is left open.
Check the compressor (Winding resistance value, loose lead wire).
Refrigeration cycle defective (Refer to after mentioned "refrigerant cycle diagnosis")
Either the outdoor fan motor abnormal current or location error was detected.
> Permanent stop.
[Diagnosis Point]
Fan motor connector loose/ defective contact.
Fan motor defective.
Controller PCB defective.
Compressor location error
Outdoor fan error
(DC motor)
0.5 sec
2 times
0.5 sec
3 times
0.5 sec
5 times
0.5 sec
6 times
0.5 sec
5 times
Содержание AW?Z24LBC
Страница 4: ...1 SPECIFICATIONS R410A CEILING WALL type INVERTER ...
Страница 6: ...2 DIMENSIONS R410A CEILING WALL type INVERTER ...
Страница 7: ... Unit mm DIMENSIONS INDOOR UNIT 02 01 Models AW Z24LBC 300 298 899 250 170 40 ...
Страница 9: ...3 REFRIGERANT SYSTEM DIAGRAM R410A CEILING WALL type INVERTER ...
Страница 11: ...4 CIRCUIT DIAGRAM R410A CEILING WALL type INVERTER ...
Страница 14: ...5 DESCRIPTION OF EACH CONTROL OPERATION R410A CEILING WALL type INVERTER ...
Страница 36: ...6 REFRIGERANT CAUTION R410A R410A CEILING WALL type INVERTER ...
Страница 53: ...IPM Protection Checking Points Check the following points and locate the cause in the outdoor unit Cause ...
Страница 63: ...9 REPLACEMENT PARTS R410A CEILING WALL type INVERTER ...
Страница 64: ...REPLACEMENT PARTS 09 01 Models AW Z24LBC ...
Страница 65: ...REPLACEMENT PARTS 09 02 Models AW Z24LBC ...
Страница 66: ...REPLACEMENT PARTS 09 03 Models AW Z24LBC ...
Страница 67: ...REPLACEMENT PARTS 09 04 Models AO Z24LBT ...
Страница 68: ...REPLACEMENT PARTS 09 05 Models AO Z24LBT ...
Страница 91: ...REPLACEMENT PARTS 09 28 PROCESS Wiring ...
Страница 92: ...REPLACEMENT PARTS 09 29 PROCESS Wiring ...
Страница 93: ...REPLACEMENT PARTS 09 30 Model AO Z24LBT PROCESS Wiring ...
Страница 94: ...10 INSTALLATION MANUAL R410A CEILING WALL type INVERTER ...
Страница 97: ...1116 Suenaga Takatsu ku Kawasaki 213 8502 Japan FEB 2007 Printed in Japan ...