8. External input and output
Terminal
(Ext. in)
CN47
(Ext. out)
Indoor unit PCB
External input and output
Connector Input select
Input
signal
External
connect kit
(Optional
parts)
External input
Operation/Stop
Forced stop
Terminal
Dry contact
Edge
—
External output
Operation status
CN47
—
—
UTY-XWZXZG
Error status
Indoor unit fan operation status
External heater output
8-1. External input
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
Indoor unit functions such as Operation/Stop can be done by using indoor unit terminals.
1
2
Terminal
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
- 33 -
8-1. External input
8. External input and output
CASSETTE TYPE
AUXG09-22KVLA
CASSETTE TYPE
AUXG09-22KVLA
Содержание AUXG09KVLA