6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit
*
1
Indoor unit is lower than outdoor unit
*
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H
H
6-1. Model: AOYG09KATA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5
7.5
10
15
Height difference H (m)
Indoor unit is higher than outdoor
unit *
1
15
—
—
—
0.903
10
—
—
0.964
0.918
7.5
—
0.988
0.968
0.922
5
0.992
0.992
0.972
0.925
0
1.000
1.000
0.980
0.933
Indoor unit is lower than outdoor
unit *
2
-5
1.000
1.000
0.980
0.933
-7.5
—
1.000
0.980
0.933
-10
—
—
0.980
0.933
-15
—
—
—
0.933
HEATING
Pipe length (m)
5
7.5
10
15
Height difference H (m)
Indoor unit is higher than outdoor
unit *
1
15
—
—
—
0.943
10
—
—
1.010
0.943
7.5
—
1.000
1.010
0.943
5
1.000
1.000
1.010
0.943
0
1.000
1.000
1.010
0.943
Indoor unit is lower than outdoor
unit *
2
-5
0.995
0.995
1.005
0.939
-7.5
—
0.993
1.002
0.936
-10
—
—
0.999
0.934
-15
—
—
—
0.925
- 65 -
6-1. Model: AOYG09KATA
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG09-22KATA
OUTDOOR UNIT
AOYG09-22KATA
Содержание AUXG09KVLA
Страница 5: ...12 1 Models AOYG09KATA AOYG12KATA AOYG14KATA AOYG18KATA and AOYG22KATA 78 CONTENTS continued ...
Страница 6: ......
Страница 7: ...Part 1 INDOOR UNIT CASSETTE TYPE AUXG09KVLA AUXG12KVLA AUXG14KVLA AUXG18KVLA AUXG22KVLA ...
Страница 56: ... 50 11 3 Others 11 Optional parts CASSETTE TYPE AUXG09 22KVLA CASSETTE TYPE AUXG09 22KVLA ...
Страница 57: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG09KATA AOYG12KATA AOYG14KATA AOYG18KATA AOYG22KATA ...