En-6

For left outlet piping (Drain 

hose), cut off the piping 

outlet cutting groove with a 

hacksaw. 

Indoor unit 

drain hose

Drain cap

Remove the drain cap by pull-

ing at the projection at the end 

of the cap with pliers, etc.

Removing the drain hose

Remove the screw at the left of 
drain hose and pull out drain hose.

Installing the drain hose

Vertically insert the drain hose toward the 
inside, so that the drain 

fi

 xture (white) can ac-

curately align with the screw hole around the 
drain cock.
After inserting and before replacing, please 
reinstall and 

fi

 x the removed screws.

•  Please hold around the joint of the drain hose during work.
•  As the screw is inside, be sure to use screwdrivers treated with magnet.

Screw

Drain 

fi

xture

Drain hose

Screw hole

Drain cock

Drain hose

Screw

Drain 

fi

xture

•   After passing the indoor piping and drain hose through the wall hole, hang the indoor unit 

on the hooks at the top and bottom of the wall hook bracket.

[Installing the indoor unit]

•  Hang the indoor unit from the hooks at the top of the wall hook bracket.
•  Insert the spacer, etc. between the indoor unit and the wall hook bracket and separate 

the bottom of the indoor unit from the wall.

Indoor unit

Wall hook bracket

(Spacer)

Connection pipe small

Align the marks

Connection pipe large

Bend 70 with a 
pipe bender

Indoor unit

Top hooks

Bottom hooks

Wall hook bracket

•  

After hooking the indoor unit to the top hook, hook the 

fi

 ttings of the indoor unit to the 2 

bottom hooks while lowering the unit and pushing it against the wall.

6.6. Flare connection (Pipe connection)

 CAUTION

 Tighten the flare nuts with a torque wrench using the specified tightening method. 

Otherwise, the 

fl

 are nuts could break after a prolonged period, causing refrigerant to leak 

and generate hazardous gas if the refrigerant comes into contact with a 

fl

 ame.

6.6.1. Flaring

Use special pipe cutter and 

fl

 are tool designed for R410A or R32 pipework.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3)  Insert the 

fl

 are nut (always use the 

fl

 are nut attached to the indoor unit(s) and outdoor unit 

or branch box respectively) onto the pipe and perform the 

fl

 are processing with a 

fl

 are 

tool. Use the special R410A or R32 

fl

 are tool, or the conventional 

fl

 are tool. Leakage of 

refrigerant may result if other 

fl

 are nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

Die

A

Pipe

B

L

Check if [L] is flared uniformly 
and is not cracked or scratched.

Pipe outside diameter 

[mm (in.)]

Dimension A [mm]

Dimension B [mm]

Flare tool for R32, 

clutch type

6.35 (1/4)

0 to 0.5

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

When using conventional 

fl

 are tools to 

fl

 are R32 pipes, the dimension A should be approx-

imately 0.5 mm more than indicated in the table (for 

fl

 aring with R32 

fl

 are tools) to achieve 

the speci

fi

 ed 

fl

 aring. Use a thickness gauge to measure the dimension A. 

Width across 

flats

Pipe outside diameter [mm (in.)]

Width across flats 

of Flare nut [mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

6.6.2. Bending pipes

•   If pipes are shaped by hand, be careful not to collapse them.
•   Bend R70 mm or more with a pipe bender.
•   Do not bend the pipes in an angle more than 90°.
•   When pipes are repeatedly bend or stretched, the material will harden, making it dif

fi

 cult 

to bend or stretch them any more.

•   Do not bend or stretch the pipes more than 3 times.

 CAUTION

 To prevent breaking of the pipe, avoid sharp bends. 

 If the pipe is bent repeatedly at the same place, it will break.

6.6.3. Pipe connection

 WARNING

The 

fl

 are connection shall not be performed indoors.

 CAUTION

 Be sure to Install the pipe against the port on the indoor unit correctly. If the centering 
is improper, the 

fl

 are nut cannot tighten smoothly. If the 

fl

 are nut is forced to turn, the 

threads will be damaged.

Do not remove the 

fl

 are nut from the indoor unit pipe until immediately before con-

necting the connection pipe.

 Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order 
to tighten the 

fl

 are nut correctly. 

Tighten the 

fl

 are nuts with a torque wrench using the speci

fi

 ed tightening method. 

Otherwise, the 

fl

 are nuts could break after a prolonged period, causing refrigerant to 

leak and generate hazardous gas if the refrigerant comes into contact with a 

fl

 ame.

Connect the piping so that the control box cover can easily be removed for servicing 
when necessary.

In order to prevent water from leaking into the control box, make sure that the piping 
is well insulated.

When the flare nut is tightened properly by your hand, hold the body side coupling with a 
wrench, then tighten with a torque wrench. (See the table below for the flare nut tightening 
torques.)

Tighten with 2 wrenches.

Holding wrench

Flare nut

Connection pipe

Torque wrench

Indoor unit pipe 
(Body side)

Flare nut [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1,100)

9333005201_IM_En_ASTG09KMCA.indd   6

9333005201_IM_En_ASTG09KMCA.indd   6

2017/1/20   11:43:05

2017/1/20   11:43:05

Содержание ASTG12CMCB

Страница 1: ...ult experienced service technicians for disconnection and reinstallation of the unit Do not place any other electrical products or household belongings under indoor unit or outdoor unit Condensation dripping from the unit might get them wet and may cause damage or malfunction of your property Be careful not to scratch the air conditioner when handling it After installation explain correct operatio...

Страница 2: ...onents During repairs to sealed components all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servic ing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation P...

Страница 3: ...hall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in satisfactory working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supp...

Страница 4: ...t piping 4 ELECTRICAL REQUIREMENT The indoor unit is powered from the outdoor unit Do not power indoor unit from separate power source WARNING Standard for electrical wiring and equipment differs in each country or region Before you start electrical working confirm related regulations codes or standards Cable Conductor size mm2 Type Remarks Connection cable 1 5 Type 60245 IEC 57 3 cable Earth Grou...

Страница 5: ... an electric discharge 6 4 Installing the wall hook bracket Remove the wall hook bracket from the indoor unit Remove 2 screws 1 Install the wall hook bracket so that it is correctly positioned horizontally and vertically If the wall hook bracket is titled water will drip to the floor 2 Install the wall hook bracket so that it is strong enough to support the weight of the unit Fasten the wall hook ...

Страница 6: ...r water from entering the pipes Die A Pipe B L Check if L is flared uniformly and is not cracked or scratched Pipe outside diameter mm in Dimension A mm Dimension B mm Flare tool for R32 clutch type 6 35 1 4 0 to 0 5 9 1 9 52 3 8 13 2 12 70 1 2 16 6 15 88 5 8 19 7 19 05 3 4 24 0 When using conventional flare tools to flare R32 pipes the dimension A should be approx imately 0 5 mm more than indicat...

Страница 7: ...lastic jacket portion but not at the insulator portion If the insulator is chafed electric leakage may occur Always connect the earth ground wire Improper earthing grounding work can cause electric shocks Do not use the earth ground screw for the indoor unit to the outdoor unit unless it is specified 7 ELECTRICAL WIRING CAUTION Be careful not to generate a spark as follows for using a flammable re...

Страница 8: ...val 2 Remove 3 caps 3 Remove wire cover 4 Remove 7 screws Screws Wire cover Screws 6 position Caps 3 position Wire cover 5 The front panel is pulled to the front raising the upper surface and a front panel is removed Front panel 9 2 Front panel installation 1 First fit the lower part of the front panel and insert top and bottom hooks 3 top sides 2 center Indoor unit Front panel Latches 2 position ...

Страница 9: ...l kit confirm whether the air conditioner receives the signal from the remote controller Do not connect the wired remote controller to the terminal for power supply When connecting the wired remote controller with the indoor unit use the connecting cable that is supplied with wired remote controller or simple remote controller Recommended cable length of wired remote controller is 10 m When you ex...

Страница 10: ...nd pull off the lock at the side of the connector insertion part CAUTION Be careful not to damage the parts on the board Otherwise it will cause malfunction Connector number CN 5 Connector number CN 4 Connector number CN 10 Connector number CN 7 Symbol indicating the location printed on the board 4 Remove the wires from the three fixtures See the figure below Leave the thick green wire in fixture ...

Страница 11: ... in the oval circles below Then connect the connectors in the squares to the terminals respectively Each terminal should form a pair with a connector CAUTION Ensure that the connector is properly inserted Otherwise it may result in erroneous operation Be careful not to damage the parts on the board Otherwise it will cause malfunction 4 Wired remote controller cable External connect kit cable sold ...

Страница 12: ...ress the RESET button to enter the function setting mode Selecting the Function Number and Setting Value Reverse cycle model 1 Press the TEMP buttons to select the func tion number Press the 10 C HEAT button to switch between the left and right digits 2 Press the POWERFUL button to proceed to setting value Press the POWERFUL button again to return to the function number selection 3 Press the TEMP ...

Страница 13: ... converter the setting cannot be made by using the remote controller Set to 00 or 01 To confirm if the remote controller has this function refer to the operating manual of each remote controller Setting record Record any changes to the settings in the following table Setting Description Setting Value Filter sign Auto restart Room temperature sensor switching Remote controller custom code External ...

Страница 14: ...peration Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 1 1 Serial communication error 1 2 Wired remote controller communication error 1 5 Check run unfinished 1 6 Peripheral unit transmission PCB connection error 1 8 External communication error 2 1 Unit number or Refrigerant circuit address setting error Simultaneous Multi 2...

Страница 15: ...rror 9 9 4 way valve error 9 10 Coil expansion valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Troubleshooting with the indoor unit display OPERATION indicator green TIMER indicator orange ECONOMY indicator green Troubleshooting ...

Страница 16: ......

Отзывы: