Fujitsu ASTG12CMCB Скачать руководство пользователя страница 2

En-2

 CAUTION

2-2 Work

•  Prior to beginning work on systems containing 

fl

 ammable refrigerants, safety checks 

are necessary to ensure that the risk of ignition is minimised. For repair to the refrig-
erating system, the precautions in 2-2 to 2-8 shall be complied with prior to conduct-
ing work on the system.

•  Work shall be undertaken under a controlled procedure so as to minimize the risk of 

fl

 ammable gas or vapour being present while the work is being performed.

•  All maintenance staff and others working in the local area shall be instructed on the 

nature of work being carried out.

•  Work in con

fi

 ned spaces shall be avoided.

•  The area around the workspace shall be sectioned off.
•  Ensure that the conditions within the area have been made safe by control of 

fl

 am-

mable material.

2-3 Checking for presence of refrigerant

•  The area shall be checked with an appropriate refrigerant detector prior to and during 

work, to ensure the technician is aware of potentially 

fl

 ammable atmospheres.

•  Ensure that the leak detection equipment being used is suitable for use with 

fl

 am-

mable refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe.

2-4 Presence of 

fi

 re extinguisher

•  If any hot work is to be conducted on the refrigeration equipment or any associated 

parts, appropriate 

fi

 re extinguishing equipment shall be available at hand. 

•  Have a dry powder or CO

2

 

fi

 re extinguisher adjacent to the charging area.

2-5 No ignition sources

•  No person carrying out work in relation to a refrigeration system which involves 

exposing any pipe work that contains or has contained 

fl

 ammable refrigerant shall 

use any sources of ignition in such a manner that it may lead to the risk of 

fi

 re or 

explosion.

•  All possible ignition sources, including cigarette smoking, should be kept suf

fi

 ciently 

far away from the site of installation, repairing, removing and disposal, during which 

fl

 ammable refrigerant can possibly be released to the surrounding space.

•  Prior to work taking place, the area around the equipment is to be surveyed to make 

sure that there are no 

fl

 ammable hazards or ignition risks. “No Smoking” signs shall 

be displayed.

2-6 Ventilated area

•  Ensure that the area is in the open or that it is adequately ventilated before breaking 

into the system or conducting any hot work.

•  A degree of ventilation shall continue during the period that the work is carried out.
•  The ventilation should safely disperse any released refrigerant and preferably expel 

it externally into the atmosphere.

2-7 Checks to the refrigeration equipment

•  Where electrical components are being changed, they shall be 

fi

 t for the purpose 

and to the correct speci

fi

 cation.

•  At all times the manufacturer’s maintenance and service guidelines shall be followed.
•  If in doubt consult the manufacturer’s technical department for assistance.
•  The following checks shall be applied to installations using 

fl

 ammable refrigerants.

-  The charge size is in accordance with the room size within which the refrigerant 

containing parts are installed.

-  The ventilation machinery and outlets are operating adequately and are not 

obstructed.

-  If an indirect refrigerating circuit is being used, the secondary circuit shall be 

checked for the presence of refrigerant. 

-  Marking to the equipment continues to be visible and legible. Markings and signs 

that are illegible shall be corrected.

-  Refrigeration pipe or components are installed in a position where they are unlikely 

to be exposed to any substance which may corrode refrigerant containing compo-
nents, unless the components are constructed of materials which are inherently 
resistant to being corroded or are suitably protected against being so corroded.

2-8 Checks to electrical devices

•  Repair and maintenance to electrical components shall include initial safety checks 

and component inspection procedures.

•  If a fault exists that could compromise safety, then no electrical supply shall be con-

nected to the circuit until it is satisfactorily dealt with.

•  If the fault cannot be corrected immediately but it is necessary to continue operation, 

an adequate temporary solution shall be used.

•  This shall be reported to the owner of the equipment so all parties are advised.
•  Initial safety checks shall include.

-  That capacitors are discharged: this shall be done in a safe manner to avoid pos-

sibility of sparking.

-  That there no live electrical components and wiring are exposed while charging, 

recovering or purging the system.

-  That there is continuity of earth bonding.

 CAUTION

3-Repairs to sealed components

•  During repairs to sealed components, all electrical supplies shall be disconnected 

from the equipment being worked upon prior to any removal of sealed covers, etc.

•  If it is absolutely necessary to have an electrical supply to equipment during servic-

ing, then a permanently operating form of leak detection shall be located at the most 
critical point to warn of a potentially hazardous situation.

•  Particular attention shall be paid to the following to ensure that by working on electri-

cal components, the casing is not altered in such a way that the level of protection is 
affected.

•  This shall include damage to cables, excessive number of connections, terminals not 

made to original speci

fi

 cation, damage to seals, incorrect 

fi

 tting of glands, etc.

•  Ensure that apparatus is mounted securely.
•  Ensure that seals or sealing materials have not degraded such that they no longer 

serve the purpose of preventing the ingress of 

fl

 ammable atmospheres.

•  Replacement parts shall be in accordance with the manufacturer’s speci

fi

 cations.

NOTE:   The use of silicon sealant may inhibit the effectiveness of some types of leak 

detection equipment.
Intrinsically safe components do not have to be isolated prior to working on 
them.

4-Repair to intrinsically safe components

•  Do not apply any permanent inductive or capacitance loads to the circuit without 

ensuring that this will not exceed the permissible voltage and current permitted for 
the equipment in use.

•  Intrinsically safe components are the only types that can be worked on while live in 

the presence of a 

fl

 ammable atmosphere. 

•  The test apparatus shall be at the correct rating.
•  Replace components only with parts speci

fi

 ed by the manufacturer.

•  Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

5-Cabling

•  Check that cabling will not be subject to wear, corrosion, excessive pressure, vibra-

tion, sharp edges or any other adverse environmental effects.

•  The check shall also take into account the effects of aging or continual vibration from 

sources such as compressors or fans.

6-Detection of 

fl

 ammable refrigerants

•  Under no circumstances shall potential sources of ignition be used in the searching 

for or detection of refrigerant leaks.

•  A halide torch (or any other detector using a naked 

fl

 ame) shall not be used.

7-Leak detection methods

•  Electronic leak detectors shall be used to detect 

fl

 ammable refrigerants, but the 

sensitivity may not be adequate, or may need re-calibration. (Detection equipment 
shall be calibrated in a refrigerant-free area.)

•  Ensure that the detector is not a potential source of ignition and is suitable for the 

refrigerant used.

•  Leak detection equipment shall be set at a percentage of the LFL of the refrigerant 

and shall be calibrated to the refrigerant employed and the appropriate percentage of 
gas (25 % maximum) is con

fi

 rmed.

• Leak detection 

fl

 uids are suitable for use with most refrigerants but the use of 

detergents containing chlorine shall be avoided as the chlorine may react with the 
refrigerant and corrode the copper pipe-work.

•  If a leak is suspected, all naked 

fl

 ames shall be removed/extinguished.

•  If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall 

be recovered from the system, or isolated (by means of shut off valves) in a part of 
the system remote from the leak. 
Oxygen free nitrogen (OFN) shall then be purged through the system both before 
and during the brazing process.

8-Removal and evacuation

•  When breaking into the refrigerant circuit to make repairs – or for any other 

purpose – conventional procedures shall be used. 
However, it is important that best practice is followed since 

fl

 ammability is a consid-

eration. 
The following procedure shall be adhered to:

• remove refrigerant
•  purge the circuit with inert gas
• evacuate
•  purge again with inert gas
•  open the circuit by cutting or brazing

•  The refrigerant charge shall be recovered into the correct recovery cylinders. 
•  The system shall be “

fl

 ushed” with OFN to render the unit safe. 

•  This process may need to be repeated several times. 
•  Compressed air or oxygen shall not be used for this task.
•  Flushing shall be achieved by breaking the vacuum in the system with OFN and 

continuing to 

fi

 ll until the working pressure is achieved, then venting to atmosphere, 

and 

fi

 nally pulling down to a vacuum. 

•  This process shall be repeated until no refrigerant is within the system. 
• When the 

fi

 nal OFN charge is used, the system shall be vented down to atmospheric 

pressure to enable work to take place.

•  This operation is absolutely vital if brazing operations on the pipe work are to take 

place.

•  Ensure that the outlet for the vacuum pump is not close to any ignition sources and 

there is ventilation available.

9333005201_IM_En_ASTG09KMCA.indd   2

9333005201_IM_En_ASTG09KMCA.indd   2

2017/1/20   11:43:03

2017/1/20   11:43:03

Содержание ASTG12CMCB

Страница 1: ...ult experienced service technicians for disconnection and reinstallation of the unit Do not place any other electrical products or household belongings under indoor unit or outdoor unit Condensation dripping from the unit might get them wet and may cause damage or malfunction of your property Be careful not to scratch the air conditioner when handling it After installation explain correct operatio...

Страница 2: ...onents During repairs to sealed components all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers etc If it is absolutely necessary to have an electrical supply to equipment during servic ing then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation P...

Страница 3: ...hall be complete with leak free disconnect couplings and in good condition Before using the recovery machine check that it is in satisfactory working order has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release Consult manufacturer if in doubt The recovered refrigerant shall be returned to the refrigerant supp...

Страница 4: ...t piping 4 ELECTRICAL REQUIREMENT The indoor unit is powered from the outdoor unit Do not power indoor unit from separate power source WARNING Standard for electrical wiring and equipment differs in each country or region Before you start electrical working confirm related regulations codes or standards Cable Conductor size mm2 Type Remarks Connection cable 1 5 Type 60245 IEC 57 3 cable Earth Grou...

Страница 5: ... an electric discharge 6 4 Installing the wall hook bracket Remove the wall hook bracket from the indoor unit Remove 2 screws 1 Install the wall hook bracket so that it is correctly positioned horizontally and vertically If the wall hook bracket is titled water will drip to the floor 2 Install the wall hook bracket so that it is strong enough to support the weight of the unit Fasten the wall hook ...

Страница 6: ...r water from entering the pipes Die A Pipe B L Check if L is flared uniformly and is not cracked or scratched Pipe outside diameter mm in Dimension A mm Dimension B mm Flare tool for R32 clutch type 6 35 1 4 0 to 0 5 9 1 9 52 3 8 13 2 12 70 1 2 16 6 15 88 5 8 19 7 19 05 3 4 24 0 When using conventional flare tools to flare R32 pipes the dimension A should be approx imately 0 5 mm more than indicat...

Страница 7: ...lastic jacket portion but not at the insulator portion If the insulator is chafed electric leakage may occur Always connect the earth ground wire Improper earthing grounding work can cause electric shocks Do not use the earth ground screw for the indoor unit to the outdoor unit unless it is specified 7 ELECTRICAL WIRING CAUTION Be careful not to generate a spark as follows for using a flammable re...

Страница 8: ...val 2 Remove 3 caps 3 Remove wire cover 4 Remove 7 screws Screws Wire cover Screws 6 position Caps 3 position Wire cover 5 The front panel is pulled to the front raising the upper surface and a front panel is removed Front panel 9 2 Front panel installation 1 First fit the lower part of the front panel and insert top and bottom hooks 3 top sides 2 center Indoor unit Front panel Latches 2 position ...

Страница 9: ...l kit confirm whether the air conditioner receives the signal from the remote controller Do not connect the wired remote controller to the terminal for power supply When connecting the wired remote controller with the indoor unit use the connecting cable that is supplied with wired remote controller or simple remote controller Recommended cable length of wired remote controller is 10 m When you ex...

Страница 10: ...nd pull off the lock at the side of the connector insertion part CAUTION Be careful not to damage the parts on the board Otherwise it will cause malfunction Connector number CN 5 Connector number CN 4 Connector number CN 10 Connector number CN 7 Symbol indicating the location printed on the board 4 Remove the wires from the three fixtures See the figure below Leave the thick green wire in fixture ...

Страница 11: ... in the oval circles below Then connect the connectors in the squares to the terminals respectively Each terminal should form a pair with a connector CAUTION Ensure that the connector is properly inserted Otherwise it may result in erroneous operation Be careful not to damage the parts on the board Otherwise it will cause malfunction 4 Wired remote controller cable External connect kit cable sold ...

Страница 12: ...ress the RESET button to enter the function setting mode Selecting the Function Number and Setting Value Reverse cycle model 1 Press the TEMP buttons to select the func tion number Press the 10 C HEAT button to switch between the left and right digits 2 Press the POWERFUL button to proceed to setting value Press the POWERFUL button again to return to the function number selection 3 Press the TEMP ...

Страница 13: ... converter the setting cannot be made by using the remote controller Set to 00 or 01 To confirm if the remote controller has this function refer to the operating manual of each remote controller Setting record Record any changes to the settings in the following table Setting Description Setting Value Filter sign Auto restart Room temperature sensor switching Remote controller custom code External ...

Страница 14: ...peration Error display Wired remote controller Error code Description OPERATION lamp green TIMER lamp orange ECONOMY lamp green 1 1 Serial communication error 1 2 Wired remote controller communication error 1 5 Check run unfinished 1 6 Peripheral unit transmission PCB connection error 1 8 External communication error 2 1 Unit number or Refrigerant circuit address setting error Simultaneous Multi 2...

Страница 15: ...rror 9 9 4 way valve error 9 10 Coil expansion valve error 10 1 Discharge temp error 10 3 Compressor temp error 10 4 High pressure error 10 5 Low pressure error 13 2 Branch boxes error Flexible Multi Display mode 0 5s ON 0 5s OFF 0 1s ON 0 1s OFF Number of flashing Troubleshooting with the indoor unit display OPERATION indicator green TIMER indicator orange ECONOMY indicator green Troubleshooting ...

Страница 16: ......

Отзывы: