8.  FUNCTION SETTING

 

CAUTION

•  Confirm whether the wiring work for outdoor unit has been finished.

•  Confirm whether the cover for electric control box on the outdoor unit is close.

 

8.1. Turning on the power

(1)  Check the remote controller wiring and DIP switch settings.
(2)  Install the front case.  

When installing the front case, connect the connector to the front case.

(3)  Check the indoor and outdoor unit wiring and circuit board switch settings, and then 

turn on the indoor and outdoor units. After “9C” has flashed on the set temperature 

display for several seconds, the clock display will appear in the center of the remote 

controller display.  

The clock display will appear in the center of the remote controller display. 

SU MO TU WE TH FR SA

8.2. Function setting

This procedure changes the function settings used to control the indoor unit according to 

the installation conditions. Incorrect settings can cause the indoor unit to malfunction. This 

procedure should be performed by authorized installation or service personnel only.

Perform the “FUNCTION SETTING” according to the installation conditions using the remote 

controller. (Refer to the indoor unit installation manual for details on the function numbers 

and setting values.)

(1)  Press the SET TEMP. buttons ( 

 ) (   ) and FAN button simultaneously for more than 

5 seconds to enter the function setting mode.

SU MO TU WE TH FR SA

(2)  Press the SET BACK button to select the indoor unit number.

SU MO TU WE TH FR SA

Unit number of INDOOR UNIT

SET BACK

(3)  Press the SET TIME ( 

 ) buttons to select the function number.

Function number

SU MO TU WE TH FR SA

(4)  Press the SET TEMP. buttons ( 

 ) (   ) to select the setting value. 

The display flashes as shown to the right during setting value selection.

Setting value

SU MO TU WE TH FR SA

(5)  Press the TIMER SET button to confirm the setting.

 

Press the TIMER SET button for a few seconds until the setting value stops flashing.

 

If the setting value display changes or if “- -” is displayed when the flashing stops, the 

setting value has not been set correctly. 

(An invalid setting value may have been selected for the indoor unit.)

(6)  Repeat steps 2 to 5 to perform additional settings.

 

Press the SET TEMP. buttons ( 

 ) (   ) and FAN button simultaneously again for 

more than 5 seconds to cancel the function setting mode. In addition, the func-

tion setting mode will be automatically canceled after 1 minute if no operation is 

performed.

(7)  After completing the FUNCTION SETTING, be sure to turn off the power and turn it on 

again.

 

CAUTION

•  After turning off the power, wait 30 seconds or more before turning on it again. The 

FUNCTION SETTING doesn’t become effective if it doesn’t do so.

• 

Function Details

(1) Filter sign

The indoor unit has a sign to inform the user that it is time to clean the filter. Select the 

time setting for the filter sign display interval in the table below according to the amount 

of dust or debris in the room. If you do not wish the filter sign to be displayed, select the 

setting value for “No indication”.

(

♦...  Factory setting)

Function  

Number

Setting 

Value

Setting Description

11

00

Standard (2500 hours)

01

Long interval (5000 hours)

02

Short interval (1250 hours)

03

No indication

(2) Cooling room temperature correction

 

Depending on the installed environment, the room temperature sensor may require a 
correction. 
The settings may be selected as shown in the table below.

(

♦...  Factory setting)

Function  

Number

Setting 

Value

Setting Description

30

00

Standard

01

Warmer control

02

Slightly lower control

03

Lower control

(3) Heating room temperature correction

Depending on the installed environment, the room temperature sensor

 

may require a 

correction.  
The settings may be changed as shown in the table below.

(

♦...  Factory setting)

Function  

Number

Setting 

Value

Setting Description

31

00

Standard

01

Warmer control

02

Slightly warmer control

03

Lower control

9379123143_IM.indb   10

10/16/2017   08:54:56

Содержание ARYG LHTA 1ph

Страница 1: ... ducto Únicamente para personal de servicio autorizado MANUALE D INSTALLAZIONE Unità interna Tipo di condotto A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Εσωτερική μονάδα Τύπος αγωγού Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Unidade interior Tipo conduta Somente para o pessoal do serviço técnico autorizado РУКОВОДСТВО ПО УСТАНОВКЕ Внутренний мод...

Страница 2: ...e display range 0 1 to 3 8 MPa Charging hose To increase pressure resistance the hose material and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 1 SAFETY PRECAUTIONS Be sure to read this Manual thoroughly before installation The warnings and precautions indica...

Страница 3: ...ise the expansion valve or capillary tube may become blocked with contaminants Improper pipe selection will degrade performance As an air conditioner using R410A in curs pressure higher than when using conventional refrigerant it is necessary to choose adequate materials Thicknesses of copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the...

Страница 4: ...nder 10 years old may approach the unit take preventive measures so that they cannot reach the unit 1 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 2 Leave the space required to service the air conditioner 3 Install the unit where connection to the outdoor unit is easy 4 Install the unit where the connection pipe can be easily installed 5 Inst...

Страница 5: ...r filter is not installed the heat exchanger may be clogged and its performance may decrease 4 4 Installing the drain hose CAUTION Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enough to prevent condensation Problems with the piping may lead to water leaks Be sure to properly insulate the drain hose so that the water will not drip fro...

Страница 6: ...ed to provide a trap for the safety drain pipe If the safety drain pipe is connected to the main drain pipe make the connection below the trap on the main drain pipe Drain pipe main Drain pipe safety Unit Once installation is complete check the flow of the drain water 5 PIPE INSTALLATION WARNING During installation make sure that the refrigerant pipe is attached firmly before you run the compresso...

Страница 7: ...electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire...

Страница 8: ...oor units by attaching an earth ground cable Unit shall be grounded in compliance with the country or region s regulations CAUTION Be sure to refer to the above diagram for do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical rules and also any specific wiring instructions or limitation 6 2 Connection cable preparation Keep the earth ground wire longer than th...

Страница 9: ...se connect the connector to the front case Screws SET BACK Front case back side Rear case Connector When remote controller cable is concealed 1 Conceal the remote controller cable 2 Pass the remote controller cable through the hole in the rear case and connect the remote controller cable to the remote controller terminal board specified in figure 3 Clamp the remote controller cable sheath with the...

Страница 10: ...R SET button for a few seconds until the setting value stops flashing If the setting value display changes or if is displayed when the flashing stops the setting value has not been set correctly An invalid setting value may have been selected for the indoor unit 6 Repeat steps 2 to 5 to perform additional settings Press the SET TEMP buttons and FAN button simultaneously again for more than 5 secon...

Страница 11: ... 1 Filter sign 2 Cooling room temperature correction 3 Heating room temperature correction 4 Auto restart 5 Indoor room temperature sensor switching function 6 External input control 7 Room temperature control switching 8 Indoor unit fan control for energy saving for cooling After completing the Function Setting be sure to turn off the power and turn it on again SETTING THE ROOM TEMPERATURE DETECT...

Страница 12: ...troller setting again NOTE When different indoor unit models are connected using the group control system some functions may no longer be available If the group control system contains multiple units that are operated simultaneously con nect and set the units as shown below Auto changeover operates under the same mode with model unit number 00 It should not be connected to any other Gr that is not...

Страница 13: ...ts free of any obstacles No cooling No heating After installation is completed has the proper operation and handling been explained to the user 11 TEST RUN CHECK ITEMS 1 Is operation of each button on the remote controller normal 2 Is the drain normal 3 Is there any abnormal noise and vibration during operation Do not operate the air conditioner in test run for a long time OPERATION METHOD For the...

Страница 14: ...le temp sensor error Indoor unit fan motor error Drain pump error Damper error Indoor unit error Outdoor unit main PCB model information error or communication error Inverter error Active filter error PFC circuit error Trip terminal L error Display PCB microcomputers communication error Discharge temp sensor error Compressor temp sensor error Outdoor unit Heat Ex liquid temp sensor error Outdoor t...

Страница 15: ...9379123143_IM indb 15 10 16 2017 08 55 11 ...

Отзывы: