background image

En-11

(4) Auto restart

 Enable or disable automatic system restart after a power outage.

(

♦...  Factory setting)

Function  

Number

Setting 

Value

Setting Description

40

00

Yes

01

No

*  Auto restart is an emergency function such as for power failure etc. Do not start and stop 

the indoor unit by this function in normal operation. Be sure to operate by the control unit, 

or external input device.

(5)  Indoor room temperature sensor switching function

(Only for Wired remote controller)
 The following settings are needed when using the Wired remote controller temperature 
sensor.

(

♦...  Factory setting)

Function  

Number

Setting 

Value

Setting Description

42

00

No

01

Yes

*  If setting value is “00” : 

 

Room temperature is controlled by the indoor unit temperature sensor.

*  If setting value is “01” : 

 

Room temperature is controlled by either indoor unit temperature sensor or remote 
controller unit sensor.

(6) External input control

 “Operation/Stop” mode or “Forced stop” mode can be selected.

(

♦...  Factory setting)

Function  

Number

Setting 

Value

Setting Description

46

00

Operation/Stop mode

01

(Setting forbidden)

02

Forced stop mode

(7) Room temperature control switching

 •  This setting is used to set the room temperature control method when the wired remote 

controller is selected by the Indoor Room Temperature Sensor Switching Function.

(

♦...  Factory setting)

Function  

Number

Setting 

Value

Setting Description

48

00

Control by the sensors of both the indoor 

unit and the wired remote controller.

01

Control only by the sensor of the wired  

remote controller

 

(8) Indoor unit fan control for energy saving for cooling

 Enables or disables the power-saving function by controlling the indoor unit fan rotation 
when the outdoor unit is stopped during cooling operation.

(

♦...  Factory setting)

Function  

Number

Setting 

Value

Setting Description

49

00

Disable

01

Enable

02

Remote controller

00:  When the outdoor unit is stopped, the indoor unit fan operates continuously following 

the setting on the remote controller.

01:  When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very 

low speed.

02:  Enable or disable this function by remote controller setting.

*  As the factory setting, this setting is initially activated.

*  When connecting VRF system using network converter, this setting must be set to “00” or “01”.

Setting record

  Record any changes to the settings in the following table.

Setting

Setting Value

(1) Filter sign
(2) Cooling room temperature correction

(3) Heating room temperature correction

(4) Auto restart
(5)  Indoor room temperature sensor switching 

function

(6) External input control

(7) Room temperature control switching

(8) Indoor unit fan control for energy saving for 

cooling

After completing the 

FUNCTION SETTING

, be sure to turn off the power and turn it on 

again.

SETTING THE ROOM TEMPERATURE DETECTION 

LOCATION

The detection location of the room temperature can be selected from the following 2 examples. 

Choose the detection location that is best for the installation location.

A.  Indoor unit setting (factory setting)

The room temperature is detected by the indoor unit temperature sensor.

(1)  When the THERMO SENSOR button is pressed, the lock display flashes because the 

function is locked at the factory.

A

Indoor unit

B.  Indoor unit/remote controller setting (room tempera-

ture sensor selection)

The temperature sensor of the indoor unit or the remote controller can be used to detect 

the room temperature.

(1)  Enable the room temperature sensor selection in FUNCTION SETTING, which will be 

“(5) Indoor room temperature sensor switching function”.

(2)  Press the THERMO SENSOR button for 5 seconds or more to select the temperature 

sensor of the indoor unit or the remote controller.

B

Indoor unit

 

CAUTION

When  select  the  “Remote  controller  setting”,  if  the  detected 

temperature  value  between  the  temperature  sensor  of  the 

indoor unit and the temperature sensor of the remote controller 

varies  significantly,  it  is  likely  to  return  to  the  control  status  of 

temperature sensor of the indoor unit temporarily.

As  the  temperature  sensor  of  remote  controller  detects  the  temperature  near 

the wall, when there is a certain difference between the room temperature and 

the  wall  temperature,  the  sensor  will  not  detect  the  room  temperature  correctly 

sometimes.

Especially when the outer side of the wall on which the sensor is positioned is 

exposed  to  the  open  air,  it  is  recommended  to  use  the  temperature  sensor  of 

the  indoor  unit  to  detect  the  room  temperature  when  the  indoor  and  outdoor 

temperature difference is significant.

The temperature sensor of the remote controller is not only used when there is a 

problem in the detection of the temperature sensor of the indoor unit.

NOTES

If the function to change the temperature sensor is used as shown in examples A (other 

than example B), be sure to lock the detection location. If the function is locked, the lock 
display 

 will flash when the THERMO SENSOR button is pressed.

9379123143_IM.indb   11

10/16/2017   08:54:58

Содержание ARYG LHTA 1ph

Страница 1: ... ducto Únicamente para personal de servicio autorizado MANUALE D INSTALLAZIONE Unità interna Tipo di condotto A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Εσωτερική μονάδα Τύπος αγωγού Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Unidade interior Tipo conduta Somente para o pessoal do serviço técnico autorizado РУКОВОДСТВО ПО УСТАНОВКЕ Внутренний мод...

Страница 2: ...e display range 0 1 to 3 8 MPa Charging hose To increase pressure resistance the hose material and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 1 SAFETY PRECAUTIONS Be sure to read this Manual thoroughly before installation The warnings and precautions indica...

Страница 3: ...ise the expansion valve or capillary tube may become blocked with contaminants Improper pipe selection will degrade performance As an air conditioner using R410A in curs pressure higher than when using conventional refrigerant it is necessary to choose adequate materials Thicknesses of copper pipes used with R410A are as shown in the table Never use copper pipes thinner than those indicated in the...

Страница 4: ...nder 10 years old may approach the unit take preventive measures so that they cannot reach the unit 1 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 2 Leave the space required to service the air conditioner 3 Install the unit where connection to the outdoor unit is easy 4 Install the unit where the connection pipe can be easily installed 5 Inst...

Страница 5: ...r filter is not installed the heat exchanger may be clogged and its performance may decrease 4 4 Installing the drain hose CAUTION Install the drain hose in accordance with the instructions in this installation manual and keep the area warm enough to prevent condensation Problems with the piping may lead to water leaks Be sure to properly insulate the drain hose so that the water will not drip fro...

Страница 6: ...ed to provide a trap for the safety drain pipe If the safety drain pipe is connected to the main drain pipe make the connection below the trap on the main drain pipe Drain pipe main Drain pipe safety Unit Once installation is complete check the flow of the drain water 5 PIPE INSTALLATION WARNING During installation make sure that the refrigerant pipe is attached firmly before you run the compresso...

Страница 7: ...electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Securely connect the connection cables to the terminal board In addition secure the cables with wiring holders Improper connections either in the wiring or at the ends of the wiring can cause a malfunction electric shock or fire...

Страница 8: ...oor units by attaching an earth ground cable Unit shall be grounded in compliance with the country or region s regulations CAUTION Be sure to refer to the above diagram for do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical rules and also any specific wiring instructions or limitation 6 2 Connection cable preparation Keep the earth ground wire longer than th...

Страница 9: ...se connect the connector to the front case Screws SET BACK Front case back side Rear case Connector When remote controller cable is concealed 1 Conceal the remote controller cable 2 Pass the remote controller cable through the hole in the rear case and connect the remote controller cable to the remote controller terminal board specified in figure 3 Clamp the remote controller cable sheath with the...

Страница 10: ...R SET button for a few seconds until the setting value stops flashing If the setting value display changes or if is displayed when the flashing stops the setting value has not been set correctly An invalid setting value may have been selected for the indoor unit 6 Repeat steps 2 to 5 to perform additional settings Press the SET TEMP buttons and FAN button simultaneously again for more than 5 secon...

Страница 11: ... 1 Filter sign 2 Cooling room temperature correction 3 Heating room temperature correction 4 Auto restart 5 Indoor room temperature sensor switching function 6 External input control 7 Room temperature control switching 8 Indoor unit fan control for energy saving for cooling After completing the Function Setting be sure to turn off the power and turn it on again SETTING THE ROOM TEMPERATURE DETECT...

Страница 12: ...troller setting again NOTE When different indoor unit models are connected using the group control system some functions may no longer be available If the group control system contains multiple units that are operated simultaneously con nect and set the units as shown below Auto changeover operates under the same mode with model unit number 00 It should not be connected to any other Gr that is not...

Страница 13: ...ts free of any obstacles No cooling No heating After installation is completed has the proper operation and handling been explained to the user 11 TEST RUN CHECK ITEMS 1 Is operation of each button on the remote controller normal 2 Is the drain normal 3 Is there any abnormal noise and vibration during operation Do not operate the air conditioner in test run for a long time OPERATION METHOD For the...

Страница 14: ...le temp sensor error Indoor unit fan motor error Drain pump error Damper error Indoor unit error Outdoor unit main PCB model information error or communication error Inverter error Active filter error PFC circuit error Trip terminal L error Display PCB microcomputers communication error Discharge temp sensor error Compressor temp sensor error Outdoor unit Heat Ex liquid temp sensor error Outdoor t...

Страница 15: ...9379123143_IM indb 15 10 16 2017 08 55 11 ...

Отзывы: