En-6

9.  FRONT PANEL REMOVAL AND INSTALLATION

Intake grill removal

Intake grill installation

b

a

Open the intake 
grille. While gently 
pressing the left 
and right mounting 
shafts of the intake 
grille outward “a”, 
remove the intake 
grille in direction of 
the arrow “b”.

c

While holding the 
grille horizontal, set 
the left and right 
mounting shafts into 
the pillow blocks at 
the top of the panel 
“c”.
To latch each shaft 
properly, insert the 
shaft until it snaps.
Press 4 places on 
the intake grille to 
close it completely.

9.1. Front panel removal

 (1)  Remove intake grille (Reference the intake grille removal.)
 (2)  Remove 3 caps.
 (3)  Remove wire cover.
 (4)  Remove 6 screws.

Screws (Wire cover )

Screws ( 6 position )

Caps ( 3 position )

Wire cover

 (5)  The front panel is pulled to the front, raising the upper surface, and a front panel is 

removed.

Front panel

9.2. Front panel installation

(1) First, 

fi

 t the lower part of the front panel, and insert top and bottom hooks. (3 top 

sides, 2 center)

Indoor unit

Front panel

Latchs (2 position)

Center hooks 
(2 position)

Top hooks
(3 position)

Top holes (6 position)

(2)  Attach the 6 screws.
(3)  Attach the wire cover.
(4)  Attach the 3 caps.
(5)  Attach the intake grille.

 CAUTION

  Install the Front panel and Intake grille securely. If installation is imperfect, the Front 

panel or Intake grille may fall off and cause injury.

10. TEST  RUN

Check items

(1)  Is operation of each button on the remote control unit normal?
(2)  Does each lamp light normally?
(3) Do 

air 

fl

 ow direction louvers operate normally?

(4)  Is the drain normal?
(5)  Do not have an abnormal noise and vibration during operation?

 

Do not operate the air conditioner in test run for a long time.

[Operation method]

  For the operation method, refer to the operating manual.

   The outdoor unit, may not operate, depending on the room temperature. In this 

case, keep on pressing the MANUAL AUTO button of the indoor unit for more than 
10 seconds. The operation indicator lamp and timer indicator lamp will begin to 

fl

 ash 

simultaneously during cooling test run. Then, heating test run will begin in about three 
minutes when HEAT is selected by the remote control operation. (Please follow the 
operating manual for remote control operation.)

 

To end test operation, press the remote controller START/STOP button.
(When the air conditioner is running by pressing the test run button, the OPERATION 
Lamp and TIMER Lamp will simultaneously 

fl

 ash slowly.)

[Using the wired remote control] (Option)

For the operation method, refer to the operating manual.
(1)  Stop the air conditioner operation.
(2)  Press the master control button and the fan control button simultaneously for 2 

seconds or more to start the test run.

Test run display

(3)  Press the start/stop button to stop the test run.

11.  REMOTE CONTROLLER INSTALLATION

 CAUTION

•  Check that the indoor unit correctly receives the signal from the remote controller, 

then install the remote controller holder.

•  Select the remote controller holder selection site by paying careful attention to the 

following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat from a stove, etc.

11.1.  Remote controller holder installation

  Install the remote controller a maximum  distance of 7 m  from the remote control re-

ceiver. However, when installing the remote controller, check that it operates correctly.

  Install the remote controller holder to a wall, pillar, etc. with the tapping screw.

remote controller 
holder 

fi

 xing

Remote 
controller holder

Tapping screw 
(small)

remote controller 
mounting

Remote 
controller

2

 Push

1

 Set

12. OPTIONAL KIT INSTALLATION (OPTION)

 This air conditioner can be connected with the following optional kits.
 •  Wired remote controller
 •  Simple remote controller
 •  External connect kit

BEFORE INSTALL WIRED REMOTE CONTROLLER

•  When you use wired remote controller, some functions may not be used.

 CAUTION

•  Before installing, be sure to disconnect all power supply.
•  Don’t touch the heat exchanger.
•  During installing or removing operation, be sure not to have wire caught by parts or 

draw it hard. Or it may result troubles to the air-conditioner.

•  Avoid place in direct sunlight.
•  Select place that will not be affected by the heat from a stove, etc
•  Before setting up the optional kit, please con

fi

 rm whether air-conditioner can receive 

the signal.

•  Do not connect the wired remote controller to the terminal for power supply.
•  When connecting the wired remote controller with the indoor unit, use the connecting 

cable (supplied with wired remote controller or simple remote controller).

•  Recommended cable length of wired remote controller is 10 m. Make sure to do 

insulate of connecting part when extended the cable.

9333005072_IM.indb   6

9333005072_IM.indb   6

2013-9-24   11:44:47

2013-9-24   11:44:47

Содержание AOYG14LMCBN

Страница 1: ...andling it After installation explain correct operation to the customer using the operating manual 2 ABOUT THE UNIT 2 1 Precautions for using R410A refrigerant The basic installation work procedures are the same as conventional refrigerant R22 models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models...

Страница 2: ...cause water leaks Use heat insulation with heat resistance above 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 80 use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80 use heat in...

Страница 3: ...lied WARNING If the wall pipe is not used the cable interconnecting the indoor unit s and outdoor unit may touch metal and cause electric discharge 6 4 Installing the wall hook bracket Remove the wall hook bracket from the indoor unit Remove 2 screws 1 Install the wall hook bracket so that it is correctly positioned horizontally and vertically If the wall hook bracket is titled water will drip to ...

Страница 4: ...re tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes Die A Pipe B L Check if L is flared uniformly and is not cracked or scratched Pipe outside diameter mm in Dimension A mm Dimension B mm Flare tool for R410A clutch type 6 35 1 4 0 to 0 5 9 1 9 52 3 8 13 2 12 70 1 2 16 6 15 88...

Страница 5: ...nnection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Connect the connection cables firmly to the terminal block Imperfect installation may cause a fire Always fasten the outside covering of the connection cable with the cable clamp If the insulator is chafed electric discharge may occur Always connect the ground wire Do not use the earth scr...

Страница 6: ... remote controller START STOP button When the air conditioner is running by pressing the test run button the OPERATION Lamp and TIMER Lamp will simultaneously flash slowly Using the wired remote control Option For the operation method refer to the operating manual 1 Stop the air conditioner operation 2 Press the master control button and the fan control button simultaneously for 2 seconds or more ...

Страница 7: ...ed White Red Black Black Insulated connection Remote controller cord Remote controller cord 20 mm 13 2 Installing wired remote controller terminal external connect kit terminal sold separately 1 Remove the screw on the control box as shown on the top right of the figure below 2 Release both bottom clasps at the sides in the direction of the arrow as circled in the bottom left of the figure below P...

Страница 8: ...fixture 1 location into the control box Control box The installation method of the control box is different for each destination country See figure below When installing reuse the screw that was removed in 13 3 2 Removing control box 2 Secure the control box with a screw Use a long screw 3 2 3 Fasten the earth wires of the heat exchanger together as shown in the left figure above Use a short screw...

Страница 9: ...ner cannot receive a cus tom code if the air conditioner has not been set for the custom code The custom codes that are set through this process are applica ble only to the signals in the FUNCTION SETTING For details on how to set the custom codes through the normal process refer to Remote controller custom code 1 Press SET TEMP button to change the custom code between Match the code on the dis pl...

Страница 10: ...e sensor change the setting to Both 01 Factory setting Setting Description Function Number Setting Value Indoor unit 42 00 Both 01 00 Sensor on the indoor unit is active 01 Sensors on both indoor unit and wired remote controller is active Remote controller custom code Only for wireless remote controller The indoor unit custom code can be changed Select the appropriate custom code Factory setting S...

Страница 11: ...t error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit er ror 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error ...

Страница 12: ......

Отзывы: