En-10

 CAUTION

After turning off the power, wait 10 seconds or more before turning on it again.

The Function Setting does not become active unless the power is turned off then on 
again.

Filter sign

 Select appropriate intervals for displaying the 

fi

 lter sign on the indoor unit according to the 

estimated amount of dust in the air of the room. 
If the indication is not required, select “No indication” (03).

(

...  Factory setting)

Setting Description 

Function 

Number

Setting Value

Standard (400 hours)

11

00

Long interval (1,000 hours)

01

Short interval (200 hours)

02

No indication

03

Room temperature control for cooling

 Depending on the installed environment, correction of the room temperature sensor may 
be required. Select the appropriate control setting according to the installed environment.

(

...  Factory setting)

Setting Description 

Function 

Number

Setting Value

Standard

30

00

Slightly lower control

01

Lower control

02

Higher control

03

Room temperature control for heating [Reverse cycle model only]

 Depending on the installed environment, correction of the room temperature sensor may 
be required. Select the appropriate control setting according to the installed environment.

(

...  Factory setting)

Setting Description 

Function 

Number

Setting Value

Standard

31

00

Lower control

01

Slightly higher control

02

Higher control

03

Auto restart

Enable or disable automatic restart after a power interruption.

(

...  Factory setting)

Setting Description

Function 

Number

Setting Value

Enable

40

00

Disable

01

*  Auto restart is an emergency function such as for power outage etc. Do not attempt to 

use this function in normal operation. Be sure to operate the unit by remote controller or 
other external input device.

Room temperature sensor switching

(Only for wireless remote controller)
When using the Wired remote controller temperature sensor, change the setting to “Both” 
(01).

(

...  Factory setting)

Setting Description

Function 

Number

Setting Value

Indoor unit

42

00

Both

01

00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller is active.

Remote controller custom code

(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.

(

...  Factory setting)

Setting Description 

Function 

Number

Setting Value

   A

44

00

B

01

C

02

D

03

External input control

 “Operation/Stop” mode or “Forced stop” mode can be selected.

(

...  Factory setting)

Setting Description 

Function 

Number

Setting Value

Operation/Stop mode

46

00

(Setting prohibited)

01

Forced stop mode

02

Indoor unit fan control for energy saving for cooling

 Enables or disables the power-saving function by controlling the indoor unit fan rotation when 
the outdoor unit is stopped during cooling operation.

(

...  Factory setting)

Setting Description 

Function 

Number

Setting Value

Disable

49

00

Enable

01

00:  When the outdoor unit is stopped, the indoor unit fan operates continuously following 

the setting on the remote controller.

01:  When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very 

low speed.

Setting record

Record any changes to the settings in the following table.

Setting Description

Setting Value

Filter sign

Room temperature control for cooling

Room temperature control for heating

Auto restart

Room temperature sensor switching

Remote controller custom code

External input control

Indoor unit fan control for energy saving for 
cooling

After completing the FUNCTION SETTING, be sure to turn off the power and turn it on 
again.

15. CUSTOMER GUIDANCE

Explain the following to the customer in accordance with the operating manual:
(1)  Starting and stopping method, operation switching, temperature adjustment, timer, air 

fl

 ow switching, and other remote control unit operations.

(2)  Air 

fi

 lter removal and cleaning, and how to use the air louvers.

(3) Give the operating manual to the customer.

9333005072_IM.indb   10

9333005072_IM.indb   10

2013-9-24   11:45:18

2013-9-24   11:45:18

Содержание AOYG14LMCBN

Страница 1: ...andling it After installation explain correct operation to the customer using the operating manual 2 ABOUT THE UNIT 2 1 Precautions for using R410A refrigerant The basic installation work procedures are the same as conventional refrigerant R22 models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models...

Страница 2: ...cause water leaks Use heat insulation with heat resistance above 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 80 use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80 use heat in...

Страница 3: ...lied WARNING If the wall pipe is not used the cable interconnecting the indoor unit s and outdoor unit may touch metal and cause electric discharge 6 4 Installing the wall hook bracket Remove the wall hook bracket from the indoor unit Remove 2 screws 1 Install the wall hook bracket so that it is correctly positioned horizontally and vertically If the wall hook bracket is titled water will drip to ...

Страница 4: ...re tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes Die A Pipe B L Check if L is flared uniformly and is not cracked or scratched Pipe outside diameter mm in Dimension A mm Dimension B mm Flare tool for R410A clutch type 6 35 1 4 0 to 0 5 9 1 9 52 3 8 13 2 12 70 1 2 16 6 15 88...

Страница 5: ...nnection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Connect the connection cables firmly to the terminal block Imperfect installation may cause a fire Always fasten the outside covering of the connection cable with the cable clamp If the insulator is chafed electric discharge may occur Always connect the ground wire Do not use the earth scr...

Страница 6: ... remote controller START STOP button When the air conditioner is running by pressing the test run button the OPERATION Lamp and TIMER Lamp will simultaneously flash slowly Using the wired remote control Option For the operation method refer to the operating manual 1 Stop the air conditioner operation 2 Press the master control button and the fan control button simultaneously for 2 seconds or more ...

Страница 7: ...ed White Red Black Black Insulated connection Remote controller cord Remote controller cord 20 mm 13 2 Installing wired remote controller terminal external connect kit terminal sold separately 1 Remove the screw on the control box as shown on the top right of the figure below 2 Release both bottom clasps at the sides in the direction of the arrow as circled in the bottom left of the figure below P...

Страница 8: ...fixture 1 location into the control box Control box The installation method of the control box is different for each destination country See figure below When installing reuse the screw that was removed in 13 3 2 Removing control box 2 Secure the control box with a screw Use a long screw 3 2 3 Fasten the earth wires of the heat exchanger together as shown in the left figure above Use a short screw...

Страница 9: ...ner cannot receive a cus tom code if the air conditioner has not been set for the custom code The custom codes that are set through this process are applica ble only to the signals in the FUNCTION SETTING For details on how to set the custom codes through the normal process refer to Remote controller custom code 1 Press SET TEMP button to change the custom code between Match the code on the dis pl...

Страница 10: ...e sensor change the setting to Both 01 Factory setting Setting Description Function Number Setting Value Indoor unit 42 00 Both 01 00 Sensor on the indoor unit is active 01 Sensors on both indoor unit and wired remote controller is active Remote controller custom code Only for wireless remote controller The indoor unit custom code can be changed Select the appropriate custom code Factory setting S...

Страница 11: ...t error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit er ror 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error ...

Страница 12: ......

Отзывы: