Fujitsu AOYG14LMCBN Скачать руководство пользователя страница 4

En-4

For left outlet piping, 

cut off the piping 

outlet cutting groove 

with a hacksaw. 

Indoor unit 

drain hose

Drain cap

Remove the drain cap by pull-

ing at the projection at the end 

of the cap with pliers, etc.

Removal method of drain hose

Remove the screw at the left of 
drain hose and pull out drain hose.

Installation method of drain hose

Vertically insert the drain hose toward the 
inside, so that the drain 

fi

 xture (white) can ac-

curately align with the screw hole around the 
drain cock.
After inserting and before replacing, please 
reinstall and 

fi

 x the removed screws.

•  Please hold around the joint of the drain hose during working.
•  As the screw is inside, be sure to use screwdriver treated with magnet.

Screw

Drain 

fi

xture

Drain hose

Screw hole

Drain cock

Drain hose

Screw

Drain 

fi

xture

• For left piping and left rear piping, align the marks on the wall hook bracket and shape the 

connection pipe.

• Bend the connection piping at a bend radius of 70 mm or more and install no more than 

35 mm from the wall.

• After passing the indoor piping and drain hose through the wall hole, hang the indoor unit on 

the hooks at the top and bottom of the wall hook bracket.

[Installing the indoor unit]

•  Hang the indoor unit from the hooks at the top of the wall hook bracket.
•  Insert the spacer, etc. between the indoor unit and the wall hook bracket and separate 

the bottom of the indoor unit from the wall.

Indoor unit

Wall hook bracket

(Spacer)

Connection pipe (6.35 mm dia.)

Align the marks

Indoor unit

Connection pipe (9.52 or 12.7 mm dia.)

Top hooks

Bottom hooks

Wall hook bracket

Bend R70 mm with 
a pipe bender

After hooking the indoor unit to the top hook, hook the 

fi

 ttings of the indoor unit to the 2 

bottom hooks while lowering the unit and pushing it against the wall.

6.6. Flare connection (Pipe connection)

 CAUTION

 Tighten the 

fl

 are nuts with a torque wrench using the speci

fi

 ed tightening method. Oth-

erwise, the 

fl

 are nuts could break after a prolonged period, causing refrigerant to leak 

and generate hazardous gas if the refrigerant comes into contact with a 

fl

 ame.

6.6.1. Flaring

Use special pipe cutter and 

fl

 are tool exclusive for R410A.

(1)  Cut the connection pipe to the necessary length with a pipe cutter.
(2)  Hold the pipe downward so that cuttings will not enter the pipe and remove any burrs.
(3)  Insert the 

fl

 are nut (always use the 

fl

 are nut attached to the indoor unit(s) and outdoor 

unit respectively) onto the pipe and perform the 

fl

 are processing with a 

fl

 are tool. Use the 

special R410A 

fl

 are tool, or the conventional 

fl

 are tool. Leakage of refrigerant may result if 

other 

fl

 are nuts are used.

(4)  Protect the pipes by pinching them or with tape to prevent dust, dirt, or water from 

entering the pipes.

Die

A

Pipe

B

L

Check if [L] is flared uniformly 
and is not cracked or scratched.

Pipe outside diameter 

[mm (in.)]

Dimension A [mm]

Dimension B

 

[mm]

Flare tool for R410A, clutch type

6.35 (1/4)

0 to 0.5

9.1

9.52 (3/8)

13.2

12.70 (1/2)

16.6

15.88 (5/8)

19.7

19.05 (3/4)

24.0

When using conventional 

fl

 are tools to 

fl

 are R410A pipes, the dimension A should be ap-

proximately 0.5 mm more than indicated in the table (for 

fl

 aring with R410A 

fl

 are tools) to 

achieve the speci

fi

 ed 

fl

 aring. Use a thickness gauge to measure the dimension A. 

Width across 

flats

Pipe outside diameter 

[mm (in.)]

Width across flats of Flare 

nut [mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

6.6.2. Bending pipes

•   If pipes are shaped by hand, be careful not to collapse them.
•   Do not bend the pipes in an angle more than 90°.
•   When pipes are repeatedly bend or stretched, the material will harden, making it dif

fi

 cult 

to bend or stretch them any more.

•   Do not bend or stretch the pipes more than 3 times.

 CAUTION

•  To prevent breaking of the pipe, avoid sharp bends. 
•  If the pipe is bent repeatedly at the same place, it will break.

6.6.3. Pipe connection

 CAUTION

•  Be sure to Install the pipe against the port on the indoor unit correctly. If the center-

ing is improper, the 

fl

 are nut cannot tighten smoothly. If the 

fl

 are nut is forced to 

turn, the threads will be damaged.

•  Do not remove the 

fl

 are nut from the indoor unit pipe until immediately before con-

necting the connection pipe.

•  Hold the torque wrench at its grip, keeping it in the right angle with the pipe, in order 

to tighten the 

fl

 are nut correctly. 

•  Tighten the 

fl

 are nuts with a torque wrench using the speci

fi

 ed tightening method. 

Otherwise, the 

fl

 are nuts could break after a prolonged period, causing refrigerant to 

leak and generate hazardous gas if the refrigerant comes into contact with a 

fl

 ame.

 CAUTION

•  Connect the piping so that the control box cover can easily be removed for servic-

ing when necessary.

•  In order to prevent water from leaking into the control box, make sure that the pip-

ing is well insulated.

When the flare nut is tightened properly by your hand, hold the body side coupling with a 
wrench, then tighten with a torque wrench. (See the table below for the flare nut tightening 
torques.)

 

Tighten with two wrenches.

Holding wrench

Flare nut

Connection pipe

Torque wrench

Indoor unit pipe 
(Body side)

Flare nut [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1,100)

9333005072_IM.indb   4

9333005072_IM.indb   4

2013-9-24   11:44:26

2013-9-24   11:44:26

Содержание AOYG14LMCBN

Страница 1: ...andling it After installation explain correct operation to the customer using the operating manual 2 ABOUT THE UNIT 2 1 Precautions for using R410A refrigerant The basic installation work procedures are the same as conventional refrigerant R22 models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models...

Страница 2: ...cause water leaks Use heat insulation with heat resistance above 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 80 use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80 use heat in...

Страница 3: ...lied WARNING If the wall pipe is not used the cable interconnecting the indoor unit s and outdoor unit may touch metal and cause electric discharge 6 4 Installing the wall hook bracket Remove the wall hook bracket from the indoor unit Remove 2 screws 1 Install the wall hook bracket so that it is correctly positioned horizontally and vertically If the wall hook bracket is titled water will drip to ...

Страница 4: ...re tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes Die A Pipe B L Check if L is flared uniformly and is not cracked or scratched Pipe outside diameter mm in Dimension A mm Dimension B mm Flare tool for R410A clutch type 6 35 1 4 0 to 0 5 9 1 9 52 3 8 13 2 12 70 1 2 16 6 15 88...

Страница 5: ...nnection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Connect the connection cables firmly to the terminal block Imperfect installation may cause a fire Always fasten the outside covering of the connection cable with the cable clamp If the insulator is chafed electric discharge may occur Always connect the ground wire Do not use the earth scr...

Страница 6: ... remote controller START STOP button When the air conditioner is running by pressing the test run button the OPERATION Lamp and TIMER Lamp will simultaneously flash slowly Using the wired remote control Option For the operation method refer to the operating manual 1 Stop the air conditioner operation 2 Press the master control button and the fan control button simultaneously for 2 seconds or more ...

Страница 7: ...ed White Red Black Black Insulated connection Remote controller cord Remote controller cord 20 mm 13 2 Installing wired remote controller terminal external connect kit terminal sold separately 1 Remove the screw on the control box as shown on the top right of the figure below 2 Release both bottom clasps at the sides in the direction of the arrow as circled in the bottom left of the figure below P...

Страница 8: ...fixture 1 location into the control box Control box The installation method of the control box is different for each destination country See figure below When installing reuse the screw that was removed in 13 3 2 Removing control box 2 Secure the control box with a screw Use a long screw 3 2 3 Fasten the earth wires of the heat exchanger together as shown in the left figure above Use a short screw...

Страница 9: ...ner cannot receive a cus tom code if the air conditioner has not been set for the custom code The custom codes that are set through this process are applica ble only to the signals in the FUNCTION SETTING For details on how to set the custom codes through the normal process refer to Remote controller custom code 1 Press SET TEMP button to change the custom code between Match the code on the dis pl...

Страница 10: ...e sensor change the setting to Both 01 Factory setting Setting Description Function Number Setting Value Indoor unit 42 00 Both 01 00 Sensor on the indoor unit is active 01 Sensors on both indoor unit and wired remote controller is active Remote controller custom code Only for wireless remote controller The indoor unit custom code can be changed Select the appropriate custom code Factory setting S...

Страница 11: ...t error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit er ror 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error ...

Страница 12: ......

Отзывы: