background image

En-2

2.3. For authorized service personnel only

 WARNING

•  For the air conditioner to operate satisfactorily, install it as outlined in this installation 

manual.

•  Connect the indoor unit and outdoor unit with the air conditioner piping and cables 

available from your local distributor. This installation manual describes the correct 
connections using the installation set available from your local distributor.

•  Installation work must be performed in accordance with national wiring standards by 

authorized personnel only.

•  Do not turn on the power until all installation work is complete.

 CAUTION

This installation manual describes how to install the indoor unit only. 
To install the outdoor unit, refer to the installation manual included with the outdoor unit.

•  Be careful not to scratch the air conditioner when handling it.
•  After installation, explain correct operation to the customer, using the operating manual.

2.4. Accessories

The following installation accessories are supplied. Use them as required.

Name and Shape

Q’ty

Name and Shape

Q’ty

Operating Manual

1

Cloth tape

1

Installation Manual 

(This manual)

1

Seal A

It is used when the diameter of 
gas pipe is Ø12.70 or more.
It is necessary when using AS14.

1

Wall hook bracket

1

Tapping screw

(M4 × 25 mm)

5

Remote controller

1

Tapping screw

(M3 × 12 mm)

2

Battery

2

Air cleaning filter

2

Remote controller holder

1

Filter holders

2

The following items are necessary to install this air conditioner. (The items are not includ-
ed with the air conditioner and must be purchased separately.)

Name Q’ty

Name Q’ty

Connection pipe assembly

1

Wall cap

1

Connection cable (4-conductor)

1

Saddle

1 set

Wall pipe

1

Drain hose

1

Decorative tape

1

Tapping screws

1 set

Vinyl tape

1

Sealant

1

2.5. Optional parts

Refer to each installation manual for the method of installing optional parts.

Parts name

Model No.

Application

Wired Remote Controller *

UTY-RVN

¾

M

For air conditioner operation

Wired Remote Controller *

UTY-RNN

¾

M

For air conditioner operation

Simple Remote Controller *

UTY-RSN

¾

M

For air conditioner operation

External connect kit *

UTY-XWZXZ5

For control input/output port

Communication kit

UTY-XCBXZ2

For the installation of optional parts

* Optional communication kit is necessary for the installation.

3. GENERAL SPECIFICATION

This INSTALLATION MANUAL brie

fl

 y outlines where and how to install the air conditioning system. 

Please read over the entire set of instructions for the indoor and outdoor units and make sure all 
accessory parts listed are with the system before beginning.

3.1. Type of copper pipe and insulation material

 CAUTION

Refer to the installation manual for the outdoor unit for description of allowable pipe 
length and height difference.

Capacity of indoor unit

Gas pipe size (thickness) 

[mm]

Liquid pipe size (thickness) 

[mm]

9, 12

Ø

 9.52 (0.8)

Ø 

6.35 (0.8)

14

Ø 12.70 (0.8)

Ø 6.35 (0.8)

 CAUTION

•  Install heat insulation around both the gas and liquid pipes. Failure to do so may 

cause water leaks.

•  Use heat insulation with heat resistance above 120 °C. Reverse cycle model only)
•  In addition, if the humidity level at the installation location of the refrigerant piping is 

expected to exceed 70%, install heat insulation around the refrigerant piping. If the 
expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and if 
the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.

•  If heat insulation is used that is not as thick as speci

fi

 ed, condensation may form on 

the surface of the insulation.

•  In addition, use heat insulation with heat conductivity of 0.045 W/(m•K) or less 20 °C.

3.2. Additional materials required for installation

A. Refrigeration (armored) tape
B. Insulated staples or clamps for connecting wire (See your local electrical codes.)
C. Putty
D. Refrigeration lubricant
E. Clamps or saddles to secure refrigerant piping

4. ELECTRICAL REQUIREMENT

The indoor unit is powered from the outdoor unit. Do not power indoor unit from separate 
power source.

 WARNING

 Refer to local codes for acceptable cable type.

Cable

Cable size

Remarks

Connection cable

Type 60245 IEC 57

(1.5 mm

2

)

3 cable + Ground, 1.5 Ø 230 V

Max. Cable Length: Limit voltage drop to less than 2%. Increase cable gauge if voltage 
drop is 2% or more.

5.  SELECTING THE MOUNTING POSITION

Decide the mounting position with the customer as follows:

5.1. Indoor unit

(1)  Install the indoor unit level on a strong wall which is not subject to vibration.
(2)  The inlet and outlet ports should not be obstructed : the air should be able to blow all 

over the room.

(3)  Install the unit a dedicated electrical branch circuit.
(4)  Do not install the unit where it will be exposed to direct sunlight.
(5)  Install the unit where connection to the outdoor unit is easy.
(6)  Install the unit where the drain pipe can be easily installed.
(7)  Take servicing, etc. into consideration and leave the spaces shown in [6.1. Installation 

dimensions]. Also install the unit where the 

fi

 lter can be removed.

Correct initial installation location is important because it is dif

fi

 cult to move unit after it is 

installed.

 WARNING

 Select installation locations that can properly support the weight of the indoor. Install 
the units securely so that they do not topple or fall.

 CAUTION

Do not install the unit in the following areas:
•  Area with high salt content, such as at the seaside. It will deteriorate metal parts, causing the 

parts to fail or the unit to leak water.

•  Area 

fi

 lled with mineral oil or containing a large amount of splashed oil or steam, such as a 

kitchen. 
It will deteriorate plastic parts, causing the parts to fail or the unit to leak water.

•  Area that generates substances that adversely affect the equipment, such as sulfuric gas, 

chlorine gas, acid, or alkali. 
It will cause the copper pipes and brazed joints to corrode, which can cause refrigerant leakage.

•  Area that can cause combustible gas to leak, contains suspended carbon 

fi

 bers or 

fl

 ammable 

dust, or volatile in

fl

 ammables such as paint thinner or gasoline.

• If gas leaks and settles around the unit, it can cause a 

fi

 re.

•  Area where animals may urinate on the unit or ammonia may be generated.

9333005072_IM.indb   2

9333005072_IM.indb   2

2013-9-24   11:44:09

2013-9-24   11:44:09

Содержание AOYG14LMCBN

Страница 1: ...andling it After installation explain correct operation to the customer using the operating manual 2 ABOUT THE UNIT 2 1 Precautions for using R410A refrigerant The basic installation work procedures are the same as conventional refrigerant R22 models However pay careful attention to the following points Since the working pressure is 1 6 times higher than that of conventional refrigerant R22 models...

Страница 2: ...cause water leaks Use heat insulation with heat resistance above 120 C Reverse cycle model only In addition if the humidity level at the installation location of the refrigerant piping is expected to exceed 70 install heat insulation around the refrigerant piping If the expected humidity level is 70 80 use heat insulation that is 15 mm or thicker and if the expected humidity exceeds 80 use heat in...

Страница 3: ...lied WARNING If the wall pipe is not used the cable interconnecting the indoor unit s and outdoor unit may touch metal and cause electric discharge 6 4 Installing the wall hook bracket Remove the wall hook bracket from the indoor unit Remove 2 screws 1 Install the wall hook bracket so that it is correctly positioned horizontally and vertically If the wall hook bracket is titled water will drip to ...

Страница 4: ...re tool Leakage of refrigerant may result if other flare nuts are used 4 Protect the pipes by pinching them or with tape to prevent dust dirt or water from entering the pipes Die A Pipe B L Check if L is flared uniformly and is not cracked or scratched Pipe outside diameter mm in Dimension A mm Dimension B mm Flare tool for R410A clutch type 6 35 1 4 0 to 0 5 9 1 9 52 3 8 13 2 12 70 1 2 16 6 15 88...

Страница 5: ...nnection cable colors with those of the outdoor unit Erroneous wiring may cause burning of the electric parts Connect the connection cables firmly to the terminal block Imperfect installation may cause a fire Always fasten the outside covering of the connection cable with the cable clamp If the insulator is chafed electric discharge may occur Always connect the ground wire Do not use the earth scr...

Страница 6: ... remote controller START STOP button When the air conditioner is running by pressing the test run button the OPERATION Lamp and TIMER Lamp will simultaneously flash slowly Using the wired remote control Option For the operation method refer to the operating manual 1 Stop the air conditioner operation 2 Press the master control button and the fan control button simultaneously for 2 seconds or more ...

Страница 7: ...ed White Red Black Black Insulated connection Remote controller cord Remote controller cord 20 mm 13 2 Installing wired remote controller terminal external connect kit terminal sold separately 1 Remove the screw on the control box as shown on the top right of the figure below 2 Release both bottom clasps at the sides in the direction of the arrow as circled in the bottom left of the figure below P...

Страница 8: ...fixture 1 location into the control box Control box The installation method of the control box is different for each destination country See figure below When installing reuse the screw that was removed in 13 3 2 Removing control box 2 Secure the control box with a screw Use a long screw 3 2 3 Fasten the earth wires of the heat exchanger together as shown in the left figure above Use a short screw...

Страница 9: ...ner cannot receive a cus tom code if the air conditioner has not been set for the custom code The custom codes that are set through this process are applica ble only to the signals in the FUNCTION SETTING For details on how to set the custom codes through the normal process refer to Remote controller custom code 1 Press SET TEMP button to change the custom code between Match the code on the dis pl...

Страница 10: ...e sensor change the setting to Both 01 Factory setting Setting Description Function Number Setting Value Indoor unit 42 00 Both 01 00 Sensor on the indoor unit is active 01 Sensors on both indoor unit and wired remote controller is active Remote controller custom code Only for wireless remote controller The indoor unit custom code can be changed Select the appropriate custom code Factory setting S...

Страница 11: ...t error 6 2 Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit er ror 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error ...

Страница 12: ......

Отзывы: