- 42 -
WA
LL
MOUN
TED
AOY
G
09-
14LZ
CAN
Outdoor unit installation in multi-row
NOTES:
• If the space is larger than stated above, the condition will be the same as when there is no
obstacle.
• Height above the floor level should be 50 mm or more.
• When installing the outdoor unit, be sure to open the front and left side to obtain better operation
efficiency.
!
CAUTION
• Do not install the outdoor unit in two-stage where the drain water could freeze. Otherwise the
drainage from the upper unit may form ice and cause a malfunction of the lower unit.
• When the outdoor temperature is 0 °C or less, do not use the accessory drain pipe and drain cap.
If the drain pipe and drain cap are used, the drain water in the pipe may freeze in extremely cold
climate. (For reverse cycle model only.)
• In area with heavy snowfall, if the inlet and outlet of the outdoor unit is blocked with snow, it might
become difficult to get warm, and it is likely to cause product malfunction. Construct a canopy and
a pedestal, or place the unit on a high stand that is locally installed.
Unit: mm
Single parallel unit arrangement
Multiple parallel unit arrangement
100 or more
200 or more
500 or more
1,000 or more
200 or more
400 or more
1,000 or more
2,000 or more
200 or more
Содержание AOYG09LZCAN
Страница 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG09LZCA ASYG12LZCA ASYG14LZCA ...
Страница 16: ... 12 WALL MOUNTED ASYG09 14LZCA 5 Wiring diagrams 5 1 Models ASYG09LZCA ASYG12LZCA and ASYG14LZCA ...
Страница 26: ... 22 WALL MOUNTED ASYG09 14LZCA 8 2 Sound level check point Microphone Microphone 1 m 0 8 m ...
Страница 41: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG09LZCAN AOYG12LZCAN AOYG14LZCAN ...
Страница 49: ... 45 WALL MOUNTED AOYG09 14LZCAN 5 Wiring diagrams 5 1 Models AOYG09LZCAN and AOYG12LZCAN ...
Страница 50: ... 46 WALL MOUNTED AOYG09 14LZCAN 5 2 Model AOYG14LZCAN ...