- 31 -
W
A
LL
MOU
N
TED
ASYG09-14LZCA
4) Auto restart
Enables or disables automatic restart after a power interruption.
NOTE:
Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or external
device.
5) Room temperature sensor switching
(Only for wired remote controller)
When using the wired remote controller temperature sensor, change the setting to "Both" (01).
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
NOTE:
Remote controller sensor must be turned on by using the remote controller.
6) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
7) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
8) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired
remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
When the setting value is set to "Both" (00), more suitable control of the room temperature is pos-
sible by setting function setting 30 and 31 too.
Function number
Setting value
Setting description
Factory setting
40
00
Enable
♦
01
Disable
Function number
Setting value
Setting description
Factory setting
42
00
Indoor unit
♦
01
Both
Function number
Setting value
Setting description
Factory setting
44
00
A
♦
01
B
02
C
03
D
Function number
Setting value
Setting description
Factory setting
46
00
Operation/Stop mode
♦
01
(Setting prohibited)
02
Forced stop mode
Function number
Setting value
Setting description
Factory setting
48
00
Both
♦
01
Wired remote controller
Содержание AOYG09LZCAN
Страница 5: ...Part 1 INDOOR UNIT WALL MOUNTED TYPE ASYG09LZCA ASYG12LZCA ASYG14LZCA ...
Страница 16: ... 12 WALL MOUNTED ASYG09 14LZCA 5 Wiring diagrams 5 1 Models ASYG09LZCA ASYG12LZCA and ASYG14LZCA ...
Страница 26: ... 22 WALL MOUNTED ASYG09 14LZCA 8 2 Sound level check point Microphone Microphone 1 m 0 8 m ...
Страница 41: ...Part 2 OUTDOOR UNIT SINGLE TYPE AOYG09LZCAN AOYG12LZCAN AOYG14LZCAN ...
Страница 49: ... 45 WALL MOUNTED AOYG09 14LZCAN 5 Wiring diagrams 5 1 Models AOYG09LZCAN and AOYG12LZCAN ...
Страница 50: ... 46 WALL MOUNTED AOYG09 14LZCAN 5 2 Model AOYG14LZCAN ...