En-14
* Auto restart is an emergency function such as for power failure etc. Do not start and stop
the indoor unit by this function in normal operation. Be sure to operate by the control unit,
or external input device.
(6) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when using the Wired remote controller temperature
sensor.
(♦... Factory setting)
Setting description
Function
number
Setting value
♦
No
42
00
Yes
01
* If setting value is “00” :
Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is “01” :
Room temperature is controlled by either indoor unit temperature sensor or remote
controller unit sensor.
(7) Wireless remote controller signal code
Change the indoor unit Signal Code, depending on the wireless remote controllers.
(♦... Factory setting)
Setting description
Function
number
Setting value
♦
A
44
00
B
01
C
02
D
03
(8) External input control
“Operation/Stop” mode or “Forced stop” mode can be selected.
(♦... Factory setting)
Setting description
Function
number
Setting value
♦
Operation/Stop mode
46
00
(Setting forbidden)
01
Forced stop mode
02
Setting record
•
Record any changes to the settings in the following table.
Setting
Setting Value
(1) Filter sign
(2) Static pressure
(3) Cooling room temperature correction
(4) Heating room temperature correction
(5) Auto restart
(6) Indoor room temperature sensor switching func
-
tion
(7) Wireless remote controller signal code
(8) External input control
After completing the
FUNCTION SETTING
, be sure to turn off the power and turn it on
again.
SETTING THE ROOM TEMPERATURE DETECTION
LOCATION
The detection location of the room temperature can be selected from the following 2 examples.
Choose the detection location that is best for the installation location.
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature sensor.
(1) When the THERMO SENSOR button is pressed, the lock display flashes because the
function is locked at the factory.
A
Indoor unit
B. Indoor unit/remote controller setting (room tempera-
ture sensor selection)
The temperature sensor of the indoor unit or the remote controller can be used to detect
the room temperature.
(1) Enable the room temperature sensor selection in FUNCTION SETTING, which will be
previous page.
(2) Press the THERMO SENSOR button for 5 seconds or more to select the temperature
sensor of the indoor unit or the remote controller.
B
Indoor unit
NOTES
If the function to change the temperature sensor is used as shown in examples A (other
than example B), be sure to lock the detection location. If the function is locked, the lock
display
will flash when the THERMO SENSOR button is pressed.
7.4. Jumper wire setting
(1) Drainage function setting (JM1)
If contained dra
in pump is not used, set the drainage function to “Invalid” in the drainage
function switching.
If contained drain pump is not use:
•
When used under “WALL MOUNTED TYPE/FLOOR STANDING CONCEALED TYPE”.
When used in natural drainage under “CEILING CONCEALED TYPE”.
(♦... Factory setting)
JM1
Drainage function
♦
Connect
Valid
Disconnect
Invalid
(2) Auto louver grille setting (JM2) (Optional parts)
(♦... Factory setting)
JM2
Auto louver grille setting
♦
Connect
Invalid
Disconnect
Valid
(3) Fan delay setting (JM3)
It is a function to delay the stop of cooling fan when the air conditioner is stopped.
(♦... Factory setting)
JM3
Fan delay
♦
Connect
Invalid
Disconnect
Valid
• Switching position
JM3
JM2
JM1
Jumper wires