En-8

5.  INSTALLING DRAIN PIPES

5.1A.  Installing drain pipes (Ceiling concealed type)

Use general hard polyvinyl chloride pipe and connect it with adhesive (polyvinyl chloride) 

so that there is no leakage.

Always heat insulate the indoor side of the drain hose.

Use a drain pipe that matches the size of the drain hose (Table A).

•  Do not perform a rise, trap and air bleeding.

•  Provide a downward gradient (1/100 or more).

•  Provide supports when long pipes are installed.

•  Use an insulation material as needed, to prevent the pipes from freezing.

•  Install the pipes in a way that allows for the removal of the control box.

Table A

O.D.

Drain pipe

32 mm(VP25)

CEILING CONCEALED TYPE (Use Drain Pump)

Outlet air

flow

Arrange the drain hose 

lower than this port.

Drain hose

Trap

OK

NO GOOD

Drain cap

NO GOOD

Rise

Air bleeding

Supporter

NO GOOD

1.5 to 2 m

OK

•  Install the drain pipe with downward gradient (1/50 to 1/100) and so there are no rises 

or traps in the pipe.

•  Use  general  hard  polyvinyl  chloride  pipe  (VP25)  [outside  diameter  32  mm]  and 

connect it with adhesive (polyvinyl chloride) so that there is no leakage.

•  When the pipe is long. Install supports.
•  Do not perform air bleeding.
•  Always heat insulate the indoor side of the drain pipe.

VP25

[O.D 32 mm

or more]

Horizontal or 

upward gradient

Supporter

Gap of 1.5-2 m

Locally arranged pipe

Max.

300 mm

700 mm or less

Rise

Air bleeding

BAD

Trap

Observe the following procedures to construct centralized drain pipe fittings

.

VP30 or more [O.D 38 mm or more]

Downward gradient 1/100 or more

700 mm or less

 

WARNING

•  Do  not  insert  the  drain  piping  into  the  sewer  where  sulfurous  gas  occurs.  (Heat 

exchange erosion may occur)

•  Insulate the parts properly so that water will not drip from the connection parts.

•  Check  for  proper  drainage  after  the  construction  by  using  the  visible  portion  of 

transparent drain port and the drain piping final outlet on the body.

 

CAUTION

•  Do not apply adhesive agent on the drain port of the body.
  (Use the attached drain hose and connect the drain piping)

5.1B.  Installing drain pipes (Wall mounted type/Floor 

standing concealed type)

 

NO GOOD

OK

NO GOOD

Rise

Trap

Drain 

cap

 

CAUTION

•  Drain  pump  cannot  be  used  if  it  is  installed  in  wall  mounted  type/floor  standing 

concealed type.

•  Set “7.4.Jumper wire setting of Drainage function setting (JM1)”.
•  Be sure to connect the pipes for drainage without leakage.
•  To avoid condensation and dripping, always insulate the indoor drain pipe.

5.2. Install the drain pipe

(1) Be sure to use supplied Drain hose 

1

 and Hose band 

2

2

 Hose band

Drain 

hole

1

 Drain hose

Hard PVC side 

• 

When drain pump is used.

 (Ceiling concealed type only)

Hose band

4 mm or less

20 mm

• 

When drain pump is not used.

 (Natural drainage)

Joint pipe 

 

(Field supply)

Drain pipe (VP25) 

 

(Field supply)

Applying 

area of 

adhesive

4 mm or less

 

CAUTION

•  When drain pump is not used, do not connect the accessory drain hose and soft PVC 

hose directly

.

9374815173-04_IM.indb   8

9/21/2011   1:45:22 PM

Содержание AOHG12LALL

Страница 1: ...zzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Duct Type h c s t u e D s i a ç n a r F l o ñ a p s E o n a i l a t I ά k I v η λ λ E s ê u g u t r o P h s i l g n E e ç k r ...

Страница 2: ...l and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 1 SAFETY PRECAUTIONS Be sure to read this Manual thoroughly before installation The warnings and precautions indicated in this Manual contain important information pertaining to your safety Be sure to observe...

Страница 3: ...ALLATION WORK 3 1 Selecting an installation location Especially the installation place is very important for the split type air conditioner because it is very difficult to move from place to place after the first installation WARNING Select installation locations that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install ...

Страница 4: ... mm or more Inlet air Inlet air Strong and durable floor Strong and durable floor 10 mm or less Right side PIPE side Right side PIPE side Grille Duct Grille Strong and durable floor 3 3A Installation the unit Ceiling concealed type WARNING Install the air conditioner in a location which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration ...

Страница 5: ...utlet side Inlet side 7000 9000 12000 14000 BTU h 18000 BTU h A 650 mm 850 mm B P200 2 400 mm P200 3 600 mm CAUTION Be sure to install the air inlet grille and the air outlet grille for air circulation The correct temperature cannot be detected Grills must be fixed so that man cannot touch indoor unit fan and exchanger and cannot be removed by only hand operation without tool Be sure to install th...

Страница 6: ...d the dew condensation Make sure to insulate between ducts and walls if metal ducts are used Please explain handling and washing methods of locally purchased materials to the customer To prevent people from touching the parts inside the unit be sure to install grilles on the inlet and outlet ports The grilles must be designed in such a way that cannot be removed without tools When connecting the d...

Страница 7: ...electing the pipe material CAUTION Do not use existing pipes Use pipes that have clean external and internal sides without any contamination which may cause trouble during use such as sulfur oxide dust cutting waste oil or water It is necessary to use seamless copper pipes Material Phosphor deoxidized seamless copper pipes It is desirable that the amount of residual oil is less than 40 mg 10 m Do ...

Страница 8: ...e careful not to collapse them Do not bend the pipes in an angle more than 90 When pipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection CAUTIO...

Страница 9: ... BAD Trap Observe the following procedures to construct centralized drain pipe fittings VP30 or more O D 38 mm or more Downward gradient 1 100 or more 700 mm or less WARNING Do not insert the drain piping into the sewer where sulfurous gas occurs Heat exchange erosion may occur Insulate the parts properly so that water will not drip from the connection parts Check for proper drainage after the con...

Страница 10: ...o avoid space with Drain hose 1 and Hose band 2 press firmly the Drain hose insulation B 3 When drain pump is used Ceiling concealed type only 3 Drain hose insulation B Ensure there is no space When drain pump is not used Natural drainage 3 Drain hose insulation B Ensure there is no space STEP1 STEP3 Butt the insulation against the unit STEP 1 Unit Slit Press firmly Press firmly STEP 2 Slit Press fi...

Страница 11: ...t the same time Otherwise electric shock or fire could result Always connect the earth cable Improper grounding work can cause electric shocks Install the remote controller cables so as not to be direct touched with your hand Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively Connect the connection cable firmly to the terminal board I...

Страница 12: ...r branch box units by attaching a earth cable Unit shall be grounded in compliance with the applicable local and national cables CAUTION Be sure to refer to the above diagram for do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical rules and also any specific wiring instructions or limitation 6 2 Connection cable preparation Keep the earth wire longer than the...

Страница 13: ...ct the connector to the front case Screws SET BACK Front case back side Rear case Connector When remote controller cable is concealed 1 Conceal the remote controller cable 2 Pass the remote controller cable through the hole in the rear case and connect the remote controller cable to the remote controller terminal board specified in figure 3 Clamp the remote controller cable sheath with the binder ...

Страница 14: ...er and turn it on again Function Details 1 Filter Sign The indoor unit has a sign to inform the user that it is time to clean the filter Select the time setting for the filter sign display interval in the table below according to the amount of dust or debris in the room If you do not wish the filter sign to be displayed select the setting value for No indication Factory setting Setting description...

Страница 15: ...oom temperature can be selected from the following 2 examples Choose the detection location that is best for the installation location A Indoor unit setting factory setting The room temperature is detected by the indoor unit temperature sensor 1 When the THERMO SENSOR button is pressed the lock display flashes because the function is locked at the factory A Indoor unit B Indoor unit remote control...

Страница 16: ...DIP SW 1 No 2 DIP SW 1 No 2 1 Normal OFF 2 Dual OFF ON 8 TEST RUN CAUTION Always turn on the power 12 hours prior to the start of the operation in order to ensure compressor protection CHECK ITEMS 1 Is operation of each button on the remote controller normal 2 Does each lamp light normally 3 Do not air flow direction louvers operate normally 4 Is the drain normal 5 Is there any abnormal noise and ...

Страница 17: ...erminals Output terminal CN103 Input No Voltage terminal CN102 Wiring arrangement Binder Medium Accessories Bind with this cable 1 9 3 Remote sensor Optional parts Connection method Connection terminals Remote sensor terminal CN8 Wiring arrangement Binder Medium Accessories Bind with this cable Remove the existing connector and replace it with the remote sensor connector ensure that the correct co...

Страница 18: ...t or optional parts for binder Use an accessory of optional parts for bushing Ceiling Avoid covering the air inlet with the wirings Binders Air inlet Binder Knockout hole Bushing Do not bind the power supply cable and other cables together CAUTION To protect the cable insulation after opening a knockout hole remove any burrs from the edge of the hole 10 CUSTOMER GUIDANCE Explain the following to t...

Страница 19: ... Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way va...