background image

En-16

9.  OPTIONAL PARTS

]

 

 

WARNING

•   

Regulation of cable differs from each locality, refer in accordance with local rules.

This  air  conditioner  can  be  connected  with  the  following  optional  kits.  Refer  to  each 

installation manual for the method of installing optional parts.

•  Wired remote controller
•  Simple remote controller
•  External connect kit
•  Remote sensor unit
•  IR Receiver unit
•  Auto louver grille

9.1. Wired remote controller (Simple remote controller)

Please refer to [6. ELECTRICAL WIRING] and [7. REMOTE CONTROLLER SETTING].

9.2. External input and external output

Connection methods

Wire modification:
Use a tool to cut off the terminal on the end of the 

wire,  and  then  remove  the  insulation  from  the  cut 

end of the wire.

Connect the wire with connecting wire with solder.

Important:

Be sure to insulate the connection between the
wires.

•  Connection terminals

Output  terminal (CN103)

Input No Voltage terminal (CN102)

•  Wiring arrangement

Binder (Medium/Accessories)

Bind with this cable.

]1

9.3. Remote sensor (Optional parts)

Connection method

•  Connection terminals

Remote sensor 

terminal (CN8)

•  Wiring arrangement

Binder (Medium/Accessories)

Bind with this cable.

•  Remove the existing connector and replace it with the remote sensor connector (ensure 

that the correct connector is used).

•  The original connector should be insulated to ensure that it does not come into contact 

with other electrical circuitry.

Setting for room temperature correction

When a remote sensor is connected, set the function setting of indoor unit as indicated 

below.

•  Set Function Number “30” (Cooling room temperature correction) to “01”
•  Set Function Number “31” (Heating room temperature correction) to “01”

1

9.4. IR Receiver Unit (Optional parts)

Connection method

•  Connection terminals

Receiver unit 

terminal (CN13)

Optional parts

 

External input/

output wire

Insulated 

connection

Cable

(Field supply)

9374815173-04_IM.indb   16

9/21/2011   1:45:28 PM

Содержание AOHG12LALL

Страница 1: ...zzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Για εξουσιοδοτημένο προσωπικό σέρβις MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВОДСТВО ПО УСТАНОВКЕ Для уполномоченного персонала KURULUM KILAVUZU Yetkili servis personeli içindir INSTALLATION MANUAL AIR CONDITIONER INDOOR UNIT Duct Type h c s t u e D s i a ç n a r F l o ñ a p s E o n a i l a t I ά k I v η λ λ E s ê u g u t r o P h s i l g n E e ç k r ...

Страница 2: ...l and base size were changed Vacuum pump A conventional vacuum pump can be used by installing a vacuum pump adapter Gas leakage detector Special gas leakage detector for HFC refrigerant R410A 1 SAFETY PRECAUTIONS Be sure to read this Manual thoroughly before installation The warnings and precautions indicated in this Manual contain important information pertaining to your safety Be sure to observe...

Страница 3: ...ALLATION WORK 3 1 Selecting an installation location Especially the installation place is very important for the split type air conditioner because it is very difficult to move from place to place after the first installation WARNING Select installation locations that can properly support the weight of the indoor Install the units securely so that they do not topple or fall CAUTION Do not install ...

Страница 4: ... mm or more Inlet air Inlet air Strong and durable floor Strong and durable floor 10 mm or less Right side PIPE side Right side PIPE side Grille Duct Grille Strong and durable floor 3 3A Installation the unit Ceiling concealed type WARNING Install the air conditioner in a location which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration ...

Страница 5: ...utlet side Inlet side 7000 9000 12000 14000 BTU h 18000 BTU h A 650 mm 850 mm B P200 2 400 mm P200 3 600 mm CAUTION Be sure to install the air inlet grille and the air outlet grille for air circulation The correct temperature cannot be detected Grills must be fixed so that man cannot touch indoor unit fan and exchanger and cannot be removed by only hand operation without tool Be sure to install th...

Страница 6: ...d the dew condensation Make sure to insulate between ducts and walls if metal ducts are used Please explain handling and washing methods of locally purchased materials to the customer To prevent people from touching the parts inside the unit be sure to install grilles on the inlet and outlet ports The grilles must be designed in such a way that cannot be removed without tools When connecting the d...

Страница 7: ...electing the pipe material CAUTION Do not use existing pipes Use pipes that have clean external and internal sides without any contamination which may cause trouble during use such as sulfur oxide dust cutting waste oil or water It is necessary to use seamless copper pipes Material Phosphor deoxidized seamless copper pipes It is desirable that the amount of residual oil is less than 40 mg 10 m Do ...

Страница 8: ...e careful not to collapse them Do not bend the pipes in an angle more than 90 When pipes are repeatedly bend or stretched the material will harden making it difficult to bend or stretch them any more Do not bend or stretch the pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection CAUTIO...

Страница 9: ... BAD Trap Observe the following procedures to construct centralized drain pipe fittings VP30 or more O D 38 mm or more Downward gradient 1 100 or more 700 mm or less WARNING Do not insert the drain piping into the sewer where sulfurous gas occurs Heat exchange erosion may occur Insulate the parts properly so that water will not drip from the connection parts Check for proper drainage after the con...

Страница 10: ...o avoid space with Drain hose 1 and Hose band 2 press firmly the Drain hose insulation B 3 When drain pump is used Ceiling concealed type only 3 Drain hose insulation B Ensure there is no space When drain pump is not used Natural drainage 3 Drain hose insulation B Ensure there is no space STEP1 STEP3 Butt the insulation against the unit STEP 1 Unit Slit Press firmly Press firmly STEP 2 Slit Press fi...

Страница 11: ...t the same time Otherwise electric shock or fire could result Always connect the earth cable Improper grounding work can cause electric shocks Install the remote controller cables so as not to be direct touched with your hand Perform wiring work in accordance with standards so that the air conditioner can be operated safely and positively Connect the connection cable firmly to the terminal board I...

Страница 12: ...r branch box units by attaching a earth cable Unit shall be grounded in compliance with the applicable local and national cables CAUTION Be sure to refer to the above diagram for do correct field wiring Wrong wiring causes malfunction of the unit Check local electrical rules and also any specific wiring instructions or limitation 6 2 Connection cable preparation Keep the earth wire longer than the...

Страница 13: ...ct the connector to the front case Screws SET BACK Front case back side Rear case Connector When remote controller cable is concealed 1 Conceal the remote controller cable 2 Pass the remote controller cable through the hole in the rear case and connect the remote controller cable to the remote controller terminal board specified in figure 3 Clamp the remote controller cable sheath with the binder ...

Страница 14: ...er and turn it on again Function Details 1 Filter Sign The indoor unit has a sign to inform the user that it is time to clean the filter Select the time setting for the filter sign display interval in the table below according to the amount of dust or debris in the room If you do not wish the filter sign to be displayed select the setting value for No indication Factory setting Setting description...

Страница 15: ...oom temperature can be selected from the following 2 examples Choose the detection location that is best for the installation location A Indoor unit setting factory setting The room temperature is detected by the indoor unit temperature sensor 1 When the THERMO SENSOR button is pressed the lock display flashes because the function is locked at the factory A Indoor unit B Indoor unit remote control...

Страница 16: ...DIP SW 1 No 2 DIP SW 1 No 2 1 Normal OFF 2 Dual OFF ON 8 TEST RUN CAUTION Always turn on the power 12 hours prior to the start of the operation in order to ensure compressor protection CHECK ITEMS 1 Is operation of each button on the remote controller normal 2 Does each lamp light normally 3 Do not air flow direction louvers operate normally 4 Is the drain normal 5 Is there any abnormal noise and ...

Страница 17: ...erminals Output terminal CN103 Input No Voltage terminal CN102 Wiring arrangement Binder Medium Accessories Bind with this cable 1 9 3 Remote sensor Optional parts Connection method Connection terminals Remote sensor terminal CN8 Wiring arrangement Binder Medium Accessories Bind with this cable Remove the existing connector and replace it with the remote sensor connector ensure that the correct co...

Страница 18: ...t or optional parts for binder Use an accessory of optional parts for bushing Ceiling Avoid covering the air inlet with the wirings Binders Air inlet Binder Knockout hole Bushing Do not bind the power supply cable and other cables together CAUTION To protect the cable insulation after opening a knockout hole remove any burrs from the edge of the hole 10 CUSTOMER GUIDANCE Explain the following to t...

Страница 19: ... Outdoor unit main PCB model information error or communication error 6 3 Inverter error 6 4 Active filter error PFC circuit error 6 5 Trip terminal L error 6 10 Display PCB microcomputers communication error 7 1 Discharge temp sensor error 7 2 Compressor temp sensor error 7 3 Outdoor unit Heat Ex liquid temp sensor error 7 4 Outdoor temp sensor error 7 5 Suction Gas temp sensor error 7 6 2 way va...

Отзывы: