En-18
11. ERROR CODES
If you use a wired type remote controller, error codes will appear on the remote
controller display. If you use a wireless remote controller, the lamps on the IR receiver
unit will output error codes by way of blinking patterns. See the lamp blinking patterns
and error codes in the table below. An error display is displayed only during operation.
Error display
Wired
remote
controller
Error code
Description
OPERATION
lamp
(green)
TIMER
lamp
(orange)
ECONOMY
lamp
(green)
●
(1)
●
(1)
◊
Serial communication error
●
(1)
●
(2)
◊
Wired remote controller
communication error
●
(1)
●
(5)
◊
Check run unfinished
●
(2)
●
(1)
◊
Unit number or Refrigerant circuit
address setting error
[Simultaneous Multi]
●
(2)
●
(2)
◊
Indoor unit capacity error
●
(2)
●
(3)
◊
Combination error
●
(2)
●
(4)
◊
Connection unit number
•
error (indoor slave unit)
[Simultaneous Multi]
Connection unit number error
•
(indoor unit or branch unit)
[Flexible Multi]
●
(2)
●
(7)
◊
Master unit, slave unit set-up
error [Simultaneous Multi]
●
(3)
●
(2)
◊
Indoor unit PCB model
information error
●
(3)
●
(5)
◊
Manual auto switch error
●
(4)
●
(1)
◊
Room temp. sensor error
●
(4)
●
(2)
◊
Indoor unit Heat Ex. Middle temp.
sensor error
●
(5)
●
(1)
◊
Indoor unit fan motor error
●
(5)
●
(3)
◊
Drain pump error
●
(5)
●
(7)
◊
Damper error
●
(5)
●
(15)
◊
Indoor unit error
●
(6)
●
(2)
◊
Outdoor unit main PCB model
information error or
communication error
●
(6)
●
(3)
◊
Inverter error
●
(6)
●
(4)
◊
Active filter error, PFC circuit
error
●
(6)
●
(5)
◊
Trip terminal L error
●
(6)
●
(10)
◊
Display PCB microcomputers
communication error
●
(7)
●
(1)
◊
Discharge temp. sensor error
●
(7)
●
(2)
◊
Compressor temp. sensor error
●
(7)
●
(3)
◊
Outdoor unit Heat Ex. liquid
temp. sensor error
●
(7)
●
(4)
◊
Outdoor temp. sensor error
●
(7)
●
(5)
◊
Suction Gas temp. sensor error
●
(7)
●
(6)
◊
2-way valve temp. sensor error
•
3-way valve temp. sensor error
•
●
(7)
●
(7)
◊
Heat sink temp. sensor error
●
(8)
●
(2)
◊
Sub-cool Heat Ex. gas inlet
•
temp. sensor error
Sub-cool Heat Ex. gas outlet
•
temp. sensor error
●
(8)
●
(3)
◊
Liquid pipe temp. sensor error
●
(8)
●
(4)
◊
Current sensor error
●
(8)
●
(6)
◊
Discharge pressure sensor
•
error
Suction pressure sensor error
•
High pressure switch error
•
●
(9)
●
(4)
◊
Trip detection
●
(9)
●
(5)
◊
Compressor rotor position
detection error (permanent stop)
●
(9)
●
(7)
◊
Outdoor unit fan motor error
●
(9)
●
(9)
◊
4-way valve error
●
(10)
●
(1)
◊
Discharge temp. error
●
(10)
●
(3)
◊
Compressor temp. error
●
(10)
●
(4)
◊
High pressure error
●
(10)
●
(5)
◊
Low pressure error
●
(13)
●
(2)
◊
Branch boxes error
[Flexible Multi]
Display mode
●
: 0.5s ON / 0.5s OFF
◊
: 0.1s ON / 0.1s OFF
( ) : Number of flashing
[Troubleshooting at the remote controller LCD]
This is possible only on the wired remote controller.
[Self-diagnosis]
If an error occurs, the following display will be shown.(“Er” will appear in the set room
temperature display.)
Error code
EX. Self-diagnosis